Specification Vitotronic 100, Type Hc1B - Viessmann VITODENS 222-F Technical Manual

Gas condensing storage combi boiler
Table of Contents

Advertisement

Control units
(cont.)
s
Programming unit:
■ Easy operation through display with large font and depiction with
good contrast
■ Removable programming unit; can be mounted as option on the
wall with separate accessory
■ Menu prompts through pictograms
■ Operating keys for:
– Navigation
– Confirmation
– Settings/menu
■ Settings:
– Boiler water temperature
– DHW temperature
– Operating program
– Codes
– Actuator tests
– Test mode
■ Displaying:
– Boiler water temperature
– DHW temperature
– Operating data
– Diagnostic details
– Fault messages
Functions
■ Electronic boiler control unit for operation at a constant boiler
water temperature
■ Room temperature-dependent operation requires a Vitotrol 100,
type UTA, UTDB or UTDB-RF (according to EnEV [Germany])
■ Heating system frost protection
■ Anti-seizing pump protection
6
■ Integral diagnostic system
■ Cylinder thermostat with priority
■ Control of solar DHW heating and central heating backup in con-
junction with the solar control module, type SM1
■ Auxiliary function for DHW heating (short-term heating to a higher
temperature)

Specification Vitotronic 100, type HC1B

Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
6 A
Protection class
I
Function type
Type 1 B to EN 60730-1
Permissible ambient temperature
– During operation
0 to +40 °C
Installation in living spaces or boiler rooms
(standard ambient conditions)
– During storage
and transport
–20 to +65 °C
VIESMANN
70
°C
4 8
A
■ Maintenance display
■ External starting and blocking (in conjunction with extension EA1)
Control characteristics
PI characteristics with modulating output
Setting the heating programs
The heating system frost protection (see frost protection function)
applies to all heating programs.
The following heating programs can be selected:
■ Heating and DHW
■ Only DHW
■ Standby mode
Frost protection function
The frost protection function is active in all heating programs.
The burner is switched ON at a boiler water temperature of 5 ºC and
will be switched OFF again at a boiler water temperature of 20 ºC.
The circulation pump will be switched ON simultaneously with the
burner and switched OFF after a delay.
The DHW cylinder will be heated to approx. 20 ºC.
To protect the system against frost, the circulation pump may be
started at certain intervals (up to 24 times per day) for periods of
approx. 10 minutes.
Summer mode
Operating program "w"
The burner starts only when the DHW cylinder needs to be heated
up.
Boiler water temperature sensor
The boiler water temperature sensor is connected to the control unit
and built into the boiler.
Specification
Sensor type
Viessmann NTC 10 kΩ at 25 °C
Permissible ambient temperature
– Operation
0 to +130 °C
– Storage and transport
–20 to +70 °C
Cylinder temperature sensor
For Vitodens with loading cylinder or solar cylinder also an additional
outlet temperature sensor.
These sensors are connected to the control unit and built into the
boiler or cylinder.
Specification
IP rating
Sensor type
Permissible ambient temperature
– During operation
– During storage and transport
Electronic tempera-
ture limiter setting
(heating mode)
82 °C (change not possible)
DHW temperature setting range
– Vitodens with
loading cylinder
10 to 63 °C
– Vitodens with
DHW cylinder
with internal indi-
rect coil
10 to 68 °C
IP 32
Viessmann NTC 10 kΩ at
25 °C
0 to +90 °C
–20 to +70 °C
VITODENS