Specification Vitocell 100-B, Type Cva - Viessmann VITOLIGNO 200-S Technical Manual

High performance wood gasification boilers for logs up to 50 cm long
Hide thumbs Also See for VITOLIGNO 200-S:
Table of Contents

Advertisement

DHW cylinder and heating water buffer cylinder

4.2 Specification Vitocell 100-B, type CVA

For DHW heating in conjunction with boilers and district heating sys-
tems, as option with electric heater as accessory for DHW cylinders
with 300 and 500 l capacity.
Suitable for the following systems:
■ DHW temperatures up to 95 °C
■ Heating water flow temperature up to 160 °C
Cylinder capacity
DIN registration number
Continuous output
for DHW heating from 10 to 45 °C
and a heating water flow tempera-
ture of ... at the heating water flow
rate stated below
Continuous output
for DHW heating from 10 to 60 °C
and a heating water flow tempera-
ture of ... at the heating water flow
rate stated below
4
Heating water flow rate for the stated contin-
uous outputs
Standby heat loss q
BS
at a temp. differential of 45 K (actual values to
DIN 4753-8).
Dimensions
Length (7)
– Incl. thermal insulation
– Excl. thermal insulation
Width
– Incl. thermal insulation
– Excl. thermal insulation
Height
– Incl. thermal insulation
– Excl. thermal insulation
Height when tilted
– Incl. thermal insulation
– Excl. thermal insulation
Installation height
Weight incl. thermal insulation
Heating water content
Heating surface
Connections (male thread)
Heating water flow and return
Cold water, DHW
DHW circulation
Information regarding continuous output
When engineering systems with the specified or calculated continuous
output, select a matching circulation pump. The stated continuous out-
put is only achieved when the rated boiler heating output ≥ continuous
output.
VIESMANN
18
l
160
90 °C
kW
40
l/h
982
80 °C
kW
32
l/h
786
70 °C
kW
25
l/h
614
60 °C
kW
17
l/h
417
50 °C
kW
9
l/h
221
90 °C
kW
36
l/h
619
80 °C
kW
28
l/h
482
70 °C
kW
19
l/h
327
m
3
/h
3.0
kWh/
1.50
24 h
a
mm
581
mm
b
mm
608
mm
c
mm
1189
mm
mm
1260
mm
mm
kg
86
l
5.5
m
2
1.0
R
1
R
¾
R
¾
(cont.)
■ Operating pressure on the heating water side up to 25 bar
(2.5 MPa)
■ Operating pressure on the DHW side up to 10 bar (1.0 MPa)
200
300
9W241/11–13 MC/E
40
53
982
1302
32
44
786
1081
25
33
614
811
17
23
417
565
9
18
221
442
36
45
619
774
28
34
482
584
19
23
327
395
3.0
3.0
1.70
2.20
581
633
608
705
1409
1746
1460
1792
97
151
5.5
10.0
1.0
1.5
1
1
¾
1
¾
1
500
750
1000
70
123
136
1720
3022
3341
58
99
111
1425
2432
2725
45
75
1106
1843
2113
32
53
786
1302
1450
24
28
589
688
810
53
102
121
911
1754
2081
44
77
756
1324
1565
33
53
567
912
1050
3.0
5.0
5.0
2.50
3.50
3.90
859
960
1060
650
750
850
923
1045
1145
837
947
1047
1948
2106
2166
1844
2005
2060
1860
2050
2100
2045
2190
2250
181
295
367
12.5
24.5
26.8
1.9
3.7
4.0
1
1
VITOLIGNO 200-S
86
59
33
91
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents