3.3.3 Aquarea basic configuration
(only needed for connection via Bus)
The HPM controller serves as a substitute for the Aquarea operating unit. Therefore,
all parameter adjustments needed for initial installation of the heat pump must be
performed via the menu structure of the HPM. This includes necessary basic
configuration and parameters as these are described in the operating and service
manuals of the Panasonic heat pump(s).
To do this, press "OK" in the default menu and open the "MCR/BMS" menu. Select
the item "heat producer" using "DOWN" and enter the menu using "OK".
Depending on the system diagram loaded (one or more heat pumps) the menu
structure of the heat pump module will either be automatically displayed, or it will be
necessary to select heat pump 1-3 by using "UP", "DOWN" and "OK".
This menu contains the most important parameters, displayed in the table below with
their default values. Some of the parameters will already have been automatically
adjusted when the system diagram was selected (e.g. DHW tank included or not):
Name
Thermos
Tank
SolarPrio
HeatPrio
Steril.
basPanH
CoolPrio
AntiFr
OpInt
TankInt
BoostDel
SterTemp
SterTime
HeaterC
OutTOn
Table 3.4: Aquarea setting parameters
After adjusting the parameters, the power supply for the heat pump must be switched
off in order to connect the adapter cable PAW-HPINT-x to the main PCB inside the
heat pump (instead of the cable coming from the operating unit) The other side of the
adapter cable must be connected to the BUS interface of the HPM controller. The heat
pump will emit a beep if the connection was successful.
3.3.4 Domestic hot water – Setpoints
If setpoints differing from the basic values (45°C) should exist for the domestic hot
water tank, these can be adjusted. Different values for occupation times 1...4 can be
selected, as well as non-occupation time and special non-occupation time (holiday).
In the menu for the heat pump, select the menu "function" using "DOWN" and
"OK".
In the "function" menu, select the menu item "Aquarea" using "DOWN" and
"OK".
In the "Aquarea" menu, select the menu "settings" using "DOWN" and "OK".
Info text
Room thermostat
Tank Connection
Solar Priority
Heating Priority
Sterilization
bas pan heater
Cooling Priority
Antifreezing
Operation Interval
Tank heat Interval
Booster Delay
Sterilisation boiling temperature
Sterilization continuing time
Heater Capacity
Outdoor temp heater on
34
Range / default value
0:no, 1:yes
0:no, 1:yes
0:no, 1:yes
0:no, 1:yes
0:no, 1:yes
0:no, 1:yes
0:no, 1:yes
0:no, 1:yes
range: 30-600 min, default: 180 min
range: 5-95 min, default: 30 min
range: 20-95 min, default: 60 min
range: 40-75 °C, default: 70 °C
range: 5-60 min, default: 10 min
range: 0, 3, 6 ,9 KW, default: 0 kW
range: -15-20 °C, default: 0 °C