Power Supply Modules - Mitsubishi MELSEC System Q Manual

Hide thumbs Also See for MELSEC System Q:
Table of Contents

Advertisement

The MELSEC System Q
3.3

Power Supply Modules

Item
Input
voltage
Power con-
sumption
Output
voltage
Output
current
The power supply modules Q63RP and Q64RP are redundant power supply modules and can
be used in combination with all CPUs except the Q00JCPU. For a system with redundant
power supply two redundant power supply modules mounted on a redundant base unit are
required. Thus the system availability is increased since the other power supply module takes
over if one power supply module fails. The redundant power supplies are "hot swappable", i.e.
can be replaced while the system is in operation (replace in RUN mode).
MELSEC System Q Beginners Manual
POW ER
MIT SU BIS HI
Q63P
Q63RP
Q61P-A1
100–120 V
24 V DC
AC
45 W
65 W
105 VA
5 V DC
6 A
8.5 A
6 A
The MELSEC System Q is powered b a DC
voltage of 5 Volts. Power supply modules
with input voltages of 24 V DC or 240 V AC
are available.
The output voltage of the power supply mod-
ule (5 V DC) is fed directly into the base unit
and is not available at external terminals.
In addition to 5 V DC the power supply mod-
ule Q62P also provides 24 DC for the supply
of peripheral devices such as sensors. This
output can be loaded with a maximum cur-
rent of 0.6 A.
Q61P-A2
Q62P
200–220 V
100–240 V AC
AC
105 VA
105 VA
5 V DC
5 V DC
24 V DC
6 A
3 A
Power Supply Modules
Q64P
Q64RP
100–120 V AC
200–240 V AC
105 VA
160 VA
5 V DC
0.6 A
8.5 A
3 – 5

Hide quick links: