Special Function Modules
CH1
CH2
CH3
CH4
(FG)
Q64RD
Temperature sensor
Resistance thermometer
(Pt100, JPt100)
Resistance thermometer
(Pt100, JPt100, Ni100)
Thermocouples type K, E, J, T, B,
R, S or N
Analog output modules
Analog output modules convert a digital value from the PLC CPU into an analog voltage or cur-
rent signal that can be used to control an external device (digital/analog conversion or D/A
conversion).
The analog output signals generated by the MELSEC System Q use the standard industrial
ranges of 0–10V and 4–20mA.
C
COM
H
1
C
COM
H
2
IN 24VDC
COM
(FG)
D/A
0~±10 V
0~20m A
MELSEC System Q Beginners Manual
Special features
b Up to 4 temperatures can be measured by one module
b The disconnection of the temperature sensor can be detected on each
channel
Q64R D
RUN
b Selection of sampling processing/time averaging processing/count
ERR.
a1
averaging processing
A1
1
B1
2
b1
3
a2
b Error compensation by offset/gain value setting
4
A2
B2
5
b2
6
a3
7
A3
8
b Alarm output when limit value is exceeded
B3
9
b3
10
a3
11
A3
b Potential isolation between process and control by means of an
12
B3
13
b3
14
SLD
15
opto-coupler is a standard feature. Additional potential isolation
16
17
between the channels for Q64TDV-GH and Q64RD-G.
18
Temperature acquisition
range
Pt100: -200 to 850°C,
JPt 100: -180 to 600°C
Pt100: -200 to 850°C,
JPt 100: -180 to 600°C,
Ni100: -60 to 180 °C
Depends on the thermo-
couple used
The resolution of 0.333 mV respectively 0.83 µA and the extremly short
conversion time of 80 µs per output channel are only two of the many fea-
tures of this modules. Isolation between process and control by means
of opto-couplers is also a standard feature.
Q62 DA
V+
All modules provide removable screw terminal blocks.
1
I+
2
V+
3
4
I+
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Das MELSEC System Q
Max. Resolution
0.025 °C
0.025 °C
B, R, S, N: 0.3°C;
K, E, J, T: 0.1°C
B: 0.7°C; R, S: 0.8°C;
K, T: 0.3 °C; E,T: 0.2°C;
J: 0.1°C; N: 0.4 °C;
Voltage: 4 μV
Module
Q64RD
Q64RD-G
Q64TD
Q64TDV-GH
3 – 33