Digital Input and Output Modules
Relay Output Modules
Electrical isolation from the internal and external circuitry is achieved by the coils and the con-
tacts of the output relays.
Modules are available as multiple outputs with isolated grouped commons or as individually
isolated "volt-free" outputs (QY18A).
Similar to the other types of output modules, the operation of the output contact is driven by the
internal CPU program. At the end of the program the PLC will refresh (update) the outputs
from the output latch memory, an LED will light and the output contact will close. The response
for the operation of the relay is approximately 10 ms.
Example for a relay output module
Item
Type of module
Number of output points
Isolation method
Rated switching voltage / current
Minimum switching load
Maximum switching voltage
Response time
Life
Maximum switching frequency
Surge suppressor
Fuse
Dielectric withstand voltage
Insulation resistance
Noise immunity
Groups of outputs
Operation indicator
External connections
Applicable wire size
Internal current consumption
(5 V DC)
Weight
MELSEC System Q Beginners Manual
Specifications
QY10
16
Relay
24 V DC, 2 A (resisitive load) per output
240 V AC, 2 A (cosϕ = 1) per output; max. 8 A per group
5 V DC, 1 mA
125 V DC / 264 V AC
OFF
ON
10 ms or less
ON
OFF
12 ms or less
Mechanical
20 million times or more
100,000 times or more @ rated switching voltage/current load
100,000 times or more @ 200 V AC, 1.5 A; 240 V AC 1 A (cos ϕ = 0.7)
300,000 times or more @ 200 V AC, 0.4 A; 240 V AC 0.3 A (cos ϕ = 0.7)
Electrical
100,000 times or more @ 200 V AC, 1 A; 240 V AC 0.5 A (cos ϕ = 0.35)
300,000 times or more @ 200 V AC, 0.3 A; 240 V AC 0.15 A (cos ϕ = 0.35)
100,000 times or more @ 24 V DC 1 A; 100 V DC 0.1 A (L/R = 0.7 ms)
300,000 times or more @ 24 V DC 0.3 A; 100 V DC 0.03 A (L/R = 0.7ms)
3600 times/hour
2830 V AC rms/3 cycles (altitude: 2000 m)
10 M or more (by insulation resistance tester)
By noise simulator of 1500 V p-p noise voltage, 1 s noise width and 25 to
60 Hz noise frequency
First transient noise IEC61000-4-4: 1kV
1 group with 16 outputs (Common terminal: terminal 17)
1 LED for each output
18-point terminal block (M3 x 6 screws)
0.3 to 0.75 mm
430 mA
0.22 kg