Condensate Drain Connection - McQuay SWP 018 Installation And Maintenance Manual

Self-contained air conditioning system type swp vintage sizes 18d thru 95d, 105e
Hide thumbs Also See for SWP 018:
Table of Contents

Advertisement

Figure7. Hot water coil pressure drop, SWP018 -
SWP040
100
10
1
10
Water Flow Rate (gpm)
Hot water coil pressure drop, SWP045 - SWP105
100
10
1
10
Water Flow Rate (gpm)
8

Condensate Drain Connection

The condensate drain connection is 1 1/8" O.D.S. copper and
is located on the same end of the unit as the condenser water
connections. The drain is internally trapped at the factory
requiring no external trap. The condensate line should be
pitched away from the unit with a minimum slope of 1/8" per
foot.
Drain pans and the drain trap should be kept clean by peri-
odic cleaning. A cleanout is provided as standard in the trap
to aid in cleaning.
200
100
200
100
IM708

Hide quick links:

Advertisement

Table of Contents
loading