X27 (Rs 422/485) Interface Of The Cp 340-Rs 422/485 - Siemens SIMATIC CP 340 User Manual

Ptp coupling and configuration
Hide thumbs Also See for SIMATIC CP 340:
Table of Contents

Advertisement

1.4.3
X27 (RS 422/485) Interface of the CP 340–RS 422/485
Definition
The X27 (RS 422/485) interface is a voltage-difference interface for serial data transmission
in compliance with the X27 standard.
Properties
The X27 (RS 422/485) interface has the following properties and fulfills the following
requirements:
Type:
Front connector:
RS 422 Signals:
RS 485 Signals:
Max. baud rate:
Max. cable length:
Standard:
Degree of protection:
Note
The X27 (RS 422/485) interface can only be run in 4-wire mode with the 3964 procedure.
PtP coupling and configuration of CP 340
Manual, 04/2011, A5E00369892-03
Differential voltage interface
15-pin sub-D female, with screwed interlock
T (A)-, R (A)-, T (B)+, R (B)+, GND;
All isolated against the S7-internal power supply
R/T (A)-, R/T (B)+, GND;
All isolated against the S7-internal power supply
19.2 kbps (3964(R) procedure)
9.6 kbps (ASCII driver, printer driver)
1,200 m, cable type LIYCY 7 0.14
DIN 66259 Parts 1 and 3, EIA-RS 422/485, CCITT V.11
IP 00
Product Description
1.4 Properties of the serial interface
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents