Event classes
The table below describes the various event classes and numbers.
Table 8- 1
Event classes and event numbers
Event no.
Event
(05)02H
Job not permitted in this CP operating mode (e.g.,
device interface not parameterized)
(05)05H
Only for printer drivers:
System data block with message texts not
available on the CP
(05)06H
Only for printer drivers:
Message text not available
(05)07H
Only for printer drivers:
Message text too long
(05)08H
Only for printer drivers:
Too many conversion statements
(05)09H
Only for printer drivers:
Too many variables
(05)0AH
Only for printer drivers:
Unknown conversion statement
(05)0BH
Only for printer drivers:
Unknown control statement
(05)0CH
Only for printer drivers:
Conversion statement not executable
(05)0DH
Only for printer drivers:
Width in conversion statement too small or too
great
(05)0EH
Only for 3964(R) and ASCII drivers:
Invalid telegram length
PtP coupling and configuration of CP 340
Manual, 04/2011, A5E00369892-03
8.2 Diagnostics Messages of the Function Blocks P_SEND, P_RCV and P_PRINT
Event class 5 (05H):
"Error while processing CPU request"
Diagnostics with the CP 340
To correct or avoid errors
Evaluate the diagnostic interrupt and rectify the error
accordingly.
Use the parameter assignment software to configure
the message texts, and then carry out a warm
restart.
Use the parameter assignment software to configure
the message texts, and then carry out a warm
restart.
Edit the message text to reduce it to a length of
fewer than 150 characters (or no more than 250
characters if it contains variables).
You have configured more conversion statements
than variables. Conversion statements without
associated variables will be ignored.
You have configured more variables than conversion
statements. Variables without associated conversion
statements will not be output.
Check the conversion statement. Undefined or
unsupported conversion statements are replaced in
the printout with ******.
Check the control statement. Undefined or
unsupported control statements will be ignored. The
control statement will not be output as text either.
Check the conversion statement. Conversion
statements that cannot be executed are output in the
printout in accordance with the defined width and the
valid remainder of the conversion statement or the
default display with * characters.
Correct the specified width of the variable in the
conversion statement on the basis of the variable's
maximum possible number of characters in text-
based display types (A, C, D, S, T, Y, Z). Only as
many characters as will fit in the specified width
appear in the printout; the text is truncated to this
width. In all other cases, * characters are output
corresponding to the width.
Telegram length is > 1,024 bytes. The rest of the
telegram (> 1,024 bytes) is still being received by the
CP 340; this means that the first part of the telegram
is discarded.
Select a shorter telegram length.