Ptp Coupling And Configuration Of Cp - Siemens SIMATIC CP 340 User Manual

Ptp coupling and configuration
Hide thumbs Also See for SIMATIC CP 340:
Table of Contents

Advertisement

Basic Principles of Serial Data Transmission
2.1 Serial Transmission of a Character
Bidirectional Data Traffic - Operating Modes
The CP 340 has two operating modes for bidirectional data traffic:
● Half-duplex operation (3964(R) procedure, ASCII driver)
● Full-duplex operation (ASCII driver)
You can choose between half-duplex operation (RS 485) and full-duplex operation (RS 422)
when using the CP 340-RS 422/485 module variant.
Asynchronous Data Transmission
With the communications processor, serial transmission occurs asynchronously. The so-
called timebase synchronism (a fixed timing code used in the transmission of a fixed
character string) is only upheld during transmission of a character. Each character to be sent
is preceded by a synchronization impulse, or start bit. The length of the start-bit transmission
determines the clock pulse. The end of the character transmission is signaled by the stop bit.
Declarations
As well as the start and stop bits, further declarations must be made between the sending
and receiving partners before serial transmission can take place. These include:
● Transmission speed (baud rate)
● Character and acknowledgment delay times
● Parity
● Number of data bits
● Number of stop bits
● Number of setup and transmission attempts permitted
Chapters "Transmission integrity (Page 30)" and "Transmission mode in Point-to-Point
Communication (Page 28)" describe the role the declarations play in the various
transmission procedures, and how they are parameterized.
24
Data are exchanged between the communication partners, but only in one direction at a
time. In half-duplex operation, therefore, at any one time data is being either sent or
received. The exception to this may be individual control characters for data flow control
(e.g. XON/XOFF), which can also be sent during a receive operation or received during a
send operation.
Data are exchanged between two or more communication partners in both directions
simultaneously. In full-duplex mode, data can be sent and received at the same time.
Every communication partner must be able to operate a send and a receive facility
simultaneously.

PtP coupling and configuration of CP 340

Manual, 04/2011, A5E00369892-03

Hide quick links: