Dhw Pump For Disinfection; Setting Up The Energy Metering; Produced Heat; Consumed Energy - Daikin ERLQ004CA Installer's Reference Manual

Altherma - low temperature split
Hide thumbs Also See for ERLQ004CA:
Table of Contents

Advertisement

5 Application guidelines

5.4.7 DHW pump for disinfection

Setup
h
c
a
i
d
b
e
a Indoor unit
b DHW tank
c DHW pump
d Heater element
e Non-return valve
f Shower
g Cold water
h Domestic hot water OUT
i Recirculation connection
The DHW pump and the installation are field supply and the
responsibility of the installer.
For the integrated DHW tank, the temperature of the DHW tank
can be set to maximum 60°C. If applicable legislation requires
higher temperature for disinfection, you can connect a DHW
pump and heater element as shown above.
If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and
heater element (if needed) as shown above.
Configuration
The indoor unit can control DHW pump operation. For more
information, see the configuration chapter.
5.5

Setting up the energy metering

Via the user interface, you can read out the following energy
data:

Produced heat

Consumed energy

You can read out the energy data:
For space heating
For space cooling
For domestic hot water production
You can read out the energy data:
Per month
Per year
5.5.1 Produced heat
Applicable for all models.
The produced heat is calculated internally based on:
The leaving and entering water temperature
The flow rate
The power consumption of the booster heater (if applicable)
in the domestic hot water tank
Setup and configuration:
No additional equipment needed.
Only in case a booster heater is present in the system,
measure its capacity (resistance measurement) and set the
capacity via the user interface. Example: If you measure a
booster heater resistance of 17.1 Ω, the capacity of the
heater at 230 V is 3100 W.
Installer reference guide
17
f
g
5.5.2 Consumed energy
You can use the following methods to determine the consumed
energy:
Calculating
Measuring
NOTICE
You cannot combine calculating the consumed energy
(example: for backup heater) and measuring the consumed
energy (example: for outdoor unit). If you do so, the energy
data will be invalid.
Calculating the consumed energy
Only applicable for EHBH/X04+08 and EHVH/X04+08.
The consumed energy is calculated internally based on:
The actual power input of the outdoor unit
The set capacity of the backup heater and booster heater
The voltage
Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via
the user interface for:
The backup heater (step 1 and step 2)
The booster heater
Measuring the consumed energy
Applicable for all models.
Preferred method because of higher accuracy.
Requires external power meters.
Setup and configuration:
For the specifications of each type of meter, see technical
data.
When using electrical power meters, set the number of
pulses/kWh for each power meter via the user interface.
Consumed energy data for EHVH/X16 and EHBH/X16
models will only be available if this setting is configured.
NOTICE
When measuring the electrical power consumption, make
sure ALL power input of the system is covered by the
electrical power meters.

5.5.3 Normal kWh rate power supply

General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/7 and X5M/8.
Power meter type
In case of...
Single-phase outdoor unit
Backup
heater
supplied
from a single-phase grid (i.e.
the backup heater model is
*3V or *9W connected to a
single-phase grid)
In other cases (i.e. a three-phase
outdoor unit and/or a 9W*
backup heater model connected
to a three-phase grid)
Use a... power meter
Single-phase
Three-phase
EHBH04+08 + ERLQ004~008

Daikin Altherma - Low Temperature Split

4P313774-1 – 2012.05

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehbh08caErlq008caEhbx04caEhbx08caEhbh04caErlq006ca

Table of Contents