8 Configuration
#
Code
[A.3.1.1.4]
[1-06]
Set weather-dependent cooling:
[1-07]
[1-08]
[1-09]
[1-08]
[1-09]
Installer reference guide
49
Description
T t
[1-06]
[1-07]
T
:
Target
leaving
t
temperature (main)
T
: Outdoor temperature
a
[1-06]:
Low
outdoor
ambient
temperature. 10°C~25°C (default:
20°C)
[1-07]:
High
outdoor
ambient
temperature. 25°C~43°C (default:
35°C)
[1-08]:
Desired
leaving
temperature when the outdoor
temperature equals or drops below
the low ambient temperature.
Between minimum and maximum
leaving water temperature (default:
22°C).
Note: This value should be higher
than [1-09] as for low outdoor
temperatures
less
cold
suffices.
[1-09]:
Desired
leaving
temperature when the outdoor
temperature equals or rises above
the high ambient temperature.
Between minimum and maximum
leaving water temperature (default:
18°C).
Note: This value should be lower
than [1-08] as for high outdoor
temperatures
colder
water
required.
Leaving water temperature: Additional zone
Only applicable if 2 leaving water temperature zones are present.
#
[A.3.1.2.1]
N/A
T a
water
water
water
water
is
Code
Description
LWT setpoint mode:
Absolute (default)
The
desired
temperature is:
NOT weather-dependent (i.e.
does not depend on the
outdoor ambient temperature)
fixed
in
scheduled)
Weather dep.: The desired leaving
water temperature is:
weather-dependent
depends
ambient temperature)
fixed
in
scheduled)
Abs + scheduled: The desired
leaving water temperature is:
NOT weather-dependent (i.e.,
does NOT depend on the
outdoor ambient temperature)
according a schedule. The
scheduled actions are On or
OFF.
Remark: This value can only
be
set
in
temperature control.
WD + scheduled: The desired
leaving water temperature is:
weather-dependent (i.e., does
depend
on
ambient temperature)
according a schedule. The
scheduled actions are On or
OFF
Remark: This value can only
be
set
in
temperature control.
EHBH04+08 + ERLQ004~008

Daikin Altherma - Low Temperature Split

leaving
water
time
(i.e.,
not
(i.e.
on
the
outdoor
time
(i.e.,
not
leaving
water
the
outdoor
leaving
water
4P313774-1 – 2012.05