Output Assemblies (Drive Consumes) - YASKAWA 1000-Series Technical Manual

Ethernet/ip
Hide thumbs Also See for 1000-Series:
Table of Contents

Advertisement

8 Output Assemblies (Drive Consumes)

8
Output Assemblies (Drive Consumes)
Note: The convention in this manual is from the PLC perspective. As such, an assembly is called an "Output Assembly" when
outputted from the PLC and received by this node. This section details "Output Assemblies" that are "Consumed" by this drive.
Basic Speed Control Output - 20 (0x14)
Output Instance
Byte
20
Name
Run Fwd
Fault Reset
Speed Reference
Extended Speed Control Output - 21 (0x15)
Output Instance
Byte
21
Name
Run Fwd
Run Rev
Fault Reset
NetCtrl
NetRef
EN 20
Bit 7
Bit 6
0
1
2
3
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2
Unit depends on o1-03.
Bit 7
Bit 6
0
NetRef
1
2
3
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Fault Reset
(0 to 1 transition: Fault Reset)
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Bit 5
Bit 4
Speed Reference (Low Byte)
Speed Reference (High Byte)
Description
(SS: Speed scale)
SS
2
= 1024 = 0x0400 Hex or 10.24 Hz
Bit 5
Bit 4
NetCtrl
Speed Reference (Low Byte)
Speed Reference (High Byte)
Description
YASKAWA ELECTRIC SIEP C730600 58A 1000-Series Option SI-EN3 Technical Manual
Bit 3
Bit 2
Fault
Reset
Bit 3
Bit 2
Fault
Reset
Bit 1
Bit 0
Run
Fwd
Bit 1
Bit 0
Run
Run
Rev
Fwd