Setup; General Information; Adjustment Elements; Setup 6.1 General Information - Vega VEGAVIB 63 Operating Instructions Manual

Contactless electronic switch
Hide thumbs Also See for VEGAVIB 63:
Table of Contents

Advertisement

Function/Configuration
Electronics and terminal
compartment
Switching point adapta-
tion (1)
VEGAVIB 63 • - contactless electronic switch
6

Setup

6.1

General information

The figures in brackets refer to the following illustrations.
On the electronics module you will find the following display and

adjustment elements:

Potentiometer for adaptation to the product density (1)
DIL switch for mode adjustment - min./max. (2)
Signal lamp (5)
Note:
As a rule, always set the mode with mode switch (2) before starting
the setup of VEGAVIB 63. The switching output will change if you set
the mode switch (2) afterwards. This could possibly trigger other con-
nected instruments or devices.
6.2
Adjustment elements
5
4
Fig. 10: Electronics and connection compartment - contactless electronic switch
1
Potentiometer for switching point adaptation
2
DIL switch for mode adjustment
3
Ground terminal
4
Connection terminals
5
Control lamp
With the potentiometer you can adapt the switching point to the solid.
It is already preset and must only be modified in special cases.
As a default setting, the potentiometer of VEGAVIB 63 is set to
the complete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light
solids you have to turn the potentiometer to the complete left posi-
tion (0.02 ... 0.1 g/cm³ or 0.0007 ... 0.0036 lbs/in³). By doing this,
6 Setup
1
2
3
19