70
7. Restore and fasten the upper mounting board in its original position, and close the AHU Kit
enclosure again (see "4.1 Installation of AHU Kit" – step 5).
Case 3: 0–10 V demand control by an external BMS
To set the thermostat for 0–10 V demand control by an external building management system
(BMS), perfom the following steps:
1. Open the AHU Kit enclosure (see "4.1 Installation of AHU Kit" – step 2), and remove the up-
per mounting board.
2. On the CZ-CAPBC2 PCB, located on the lower mounting board inside the AHU Kit en-
closure, remove the existing wiring from the thermostat TR-16 at the analogue input (AI)
contacts No. 3 and 4, and replace it with the 0–10 V signal wiring from the external BMS
(see diagram below). Make sure that correct polarity is observed: terminal 3 = negative (–),
terminal 4 = positive (+).
TERMINAL
COM DI1 DI2 DI3 COM DO2 COM DO1
+
1
2
3
4
+
E
1
ORG
2
RED
3
YEL
T10
(YEL)
4
BLK
GRY
5
6
WHT
Connect 0–10 V signal wiring from
BMS here (observing correct polarity!)
BRN
ORG
YEL
BLU
COM DO2 COM DO1
CN2
CZ-CAPBC2
5
6
7
8
9
10
11
12
8
9
10
PK1-B
PAW-T10
1
1
2
2
3
4POL
T10
3
4
(WHT)
4
5
6
PK1-A
7 6 5
-
+
13
14
15
CN1
5
4
3
2
1
TR-16
10
9
8
7
6
Disconnect the
wiring of the
TERMINAL
TR-16 controller
PT10 PT9 PT8
PT100