Panasonic PAW560MAH2L Installation Instructions Manual page 52

Air handling unit kit
Table of Contents

Advertisement

Electrical Wiring
Wiring system diagram – PACi systems
For single-phase outdoor units
Power supply
220 – 240V ~50/60Hz
For three-phase outdoor units
Power supply
220 – 240V ~50/60Hz
Notes on wiring system diagrams – All systems
1. Refer to the previous section (Recommended wire lengths and diameters) for
2. The connection diagram below shows the power supply connector (Section D)
3. Refrigerant Circuit (R.C.) address should be set on the outdoor unit before turn-
4. Regarding R.C. address setting, refer to the installation instructions supplied
5. Use shielded wires for inter-unit control wiring (C) with shielded woven mesh
52
Ground
Remote
controller
WHT
BLK
Ground
Ground
Ground
Remote
controller
WHT
BLK
Ground
Ground
the explanation of "A", "B", "C", "D", "E" and "F" in the above diagrams.
of the AHU Kit's terminal board (actual appearance may differ slightly).
10P Connector / Section D
1
2 3 4 5
6 7
8 9 10
ing the power on.
with the remote controller unit. Auto address setting can be executed by remote
controller automatically. Refer to the installation instructions supplied with the
remote controller unit.
grounded on both sides, otherwise misoperation from noise may occur.
Shielded wire
Ground
Connect wiring as shown in the section "Wiring System Diagram".
AHU Kit
Outdoor unit
Ground
AHU Kit
Outdoor unit
INV unit
Ground
1 L
Power supply
2 N
Neutral conductor
3 PE Protective earthing
4 IZ-5 Blower out
5 IZ-3 Blower out
Ground
INV unit
Power supply
220 – 240V ~50/60Hz
Ground
Power supply
380 – 415V 3N ~50/60Hz
Ground
6 OP3 Blower protection
7 2Z-7 Blower protection
8 HU1 Humidifier
9 HU2 Humidifier
10 Blind

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Paw560mah2Paw280pah2lPaw280pah2Paw280mah2lPaw280mah2