Recommended Wire Lengths And Diameters - Panasonic PAW560MAH2L Installation Instructions Manual

Air handling unit kit
Table of Contents

Advertisement

Electrical Wiring
5.2

Recommended wire lengths and diameters

i
Important
● The letter coding (A to F) used in the following tables refers to the wiring system
● For information on "(A) Power supply of outdoor unit" refer to the "Installation
Indoor unit
Control wiring
(between outdoor and indoor units
0.75 mm
(AWG# 18)
Use shielded wiring*
Max. 1,000 m
1 "E" and "F" are relevant for ECOi multi connection systems only.
50
diagrams in the next section.
Instructions" for the relevant outdoor unit.
Type
AHU Kit
(C) Inter-unit control wiring
or
2.0 mm
2
(AWG# 14)
Use shielded wiring*
Max. 2,000 m
(B) Power supply
2.5 mm
(AWG#13)
2
Max. 150 m
(D) Remote
control wiring
0.75 mm
2
2
(AWG# 18)
Use shielded wiring*
Max. 500 m
Time delay fuse or circuit breaker
10 – 16 A
(E) Control wiring
(F) Inter-outdoor-
for group control
unit control wiring
1
0.75 mm
0.75 mm
2
(AWG# 18)
(AWG# 18)
Use shielded wiring*
Use shielded wiring*
Max. 200 m (total)
Max. 300 m
1
2