Processing Of Command Variable And Formation Of Negative Deviation - Siemens SIPART DR20 Project Planning Manual

Compact controller
Table of Contents

Advertisement

Project Planning Manual
In the following, the defined (adjustable using the pushbuttons 12) ratio factor is referred to as the
setpoint ratio w
and indicated as the setpoint on the digital display. The range of adjustment of the
v
ratio factor v is defined by the parameters w
LA < w
and LE > w
a
e
The current ratio is referred to as the actual ratio xv and is obtained by reversing the ratio formula:
It is indicated as the actual value in the digital display and used for x-tracking if applicable.
The display range for ratio factors is 0.000 to 9.999 (negative values are suppressed) The negative
deviation display indicates xd = w - x as with the other controller types.
The setpoint ramp Tw is only effective at OFF or from 1 to 100 s. The alarm function enables
monitoring of the actual ratio or the setpoint ratio.
INT
INT
gn
w
w
SP - w
w
vi
x2
x1 - c1
=
x2
x1
A = H or N or Bl or Si
1)
S22 = 0, effective starting with software version A09
Fig. 3/15
Processing of command variable and formation of negative deviation in ratio controller
38
.
A
A
w
w
va
ve
0
1
S17
x2
x
- tracking
v
x
v
x
v
x1
and w
within the limits 0.000 and 9.999 where
a
e
x
= (x1 - c1) / x2
v
T
w
Key
8 8 8 8
∗ x2 + c1 = w
w
v
8 8 8 4
Display
W
0
0
0 0
X
S20 = 1, S21
+
1)
S23
-
0
1
2
S22
a1 a2
SIPART DR20
+
Xd
-
A2
A1