Project Planning Manual
In the following, the defined (adjustable using the pushbuttons 12) ratio factor is referred to as the
setpoint ratio w
and indicated as the setpoint on the digital display. The range of adjustment of the
v
ratio factor v is defined by the parameters w
LA < w
and LE > w
a
e
The current ratio is referred to as the actual ratio xv and is obtained by reversing the ratio formula:
It is indicated as the actual value in the digital display and used for x-tracking if applicable.
The display range for ratio factors is 0.000 to 9.999 (negative values are suppressed) The negative
deviation display indicates xd = w - x as with the other controller types.
The setpoint ramp Tw is only effective at OFF or from 1 to 100 s. The alarm function enables
monitoring of the actual ratio or the setpoint ratio.