External alarm indicator
Battery
Connections
Environmental conditions
Mechanical data
Standards
Building Technologies
Fire Safety & Security Systems
connectable ext. AI
Power
Voltage
Length of line
Flashing interval times light / dark
Number of batteries
Voltage
Type
Lithium:
Capacity
Service life
Battery voltage monitored
Detector line and ext. AI:
Design
Wire cross-section
MC-Link
Operating temperature
Storage temperature
Air humidity
Protection category
(EN60529/IEC529)
Electromagnetic compatibility:
1 MHz ... 2 GHz
Dimensions (L x W x H)
Weight without battery
Color
Material
Combustibility
Standards
Approvals
QS standards
CE conformity mark
2
9 ... 15 mA
6 ... 17 VDC
max. 30 m with unshielded cables
(recommended), or when the shielding is
connected to the positive pole of the AI on
the detector base
max. 5 m, if the shielding is connected with
the earth
32 ms / 1 s
1
9 VDC
Block / 6LR61
1200 mAh
>5 years
yes
Spring clips
2
0.2 ... 1.5 mm
Plug-type connection
-10 ... +55 °C
-30 ... +65 °C
≤95 % rel.
IP40
30 V/m
214 x 58 x 33 mm
0.190 kg
similar to RAL 9002 grey-white
PC Macrolon 9125
UL94 V-1
EN54-17:2005
EN54-18:2005
VdS G207043
Siemens Standard SN 36350
ISO9001
ISO9004
yes
0786-CPD-20283