Exchange Radio Detectors - Siemens FDCW221 Technical Manual

Radio gateway
Hide thumbs Also See for FDCW221:
Table of Contents

Advertisement

9.8

Exchange radio detectors

Building Technologies
Fire Safety & Security Systems
The items 2 to 4 listed below, regarding the replacement of a radio detector, can be
found in the chapter in account.
Procedure:
1. Switch the FDnet detector line off.
2. Log the existing radio detector off the radio gateway.
3. Replace the radio detector.
4. Register the new radio detector at the radio gateway.
5. Switch the FDnet detector line back on.
6. Select 'Accept replaced devices' on the control panel.
Replace only one radio detector at once.
see also:
8.3 Register the radio detector at the radio gateway, Page 34
8.5 Logging off a radio detector at the radio gateway., Page 37
Maintenance / Troubleshooting
009865_b_en_--.doc