Features - Siemens FDCW221 Technical Manual

Radio gateway
Hide thumbs Also See for FDCW221:
Table of Contents

Advertisement

Features

3
Features
10
Building Technologies
Fire Safety & Security Systems
With the radio gateway it is possible to monitor signals emitted by radio detectors
and to send them to a fire control panel via the FDnet.
The radio gateway is operated on the FDnet. The term "Radio detectors"
comprises all devices that can be monitored by the radio gateway.
The radio gateway FDCW221 may communicate with the following radio detectors:
Radio smoke detector DOW1171
Manual call point with radio base SMF6120
A radio cell is made up of a radio gateway and the radio detectors registered on it.
The following figure shows how the radio gateway is integrated into the fire
detection system via the FDnet.
FDCW221
DOW1171
DOW1171
Fig. 1
Radio gateway on the FDnet with radio detectors
Features
compatible with the fire detection system FS20
simultaneous operation of wired fire detectors on the FDnet and wireless radio
detectors on the radio gateway is possible
high transmission reliability
automatic definition of the optimum basic and secondary radio channels
automatic change of channels in case of radio interferences
Individual addressing for easy identification of the location
up to 16 radio gateways with radio cell monitoring function can be operated
up to 30 radio detectors can be connected to one radio gateway
2 external alarm indicators can be connected to the radio gateway
low current consumption; battery change only required after 5 years
Applications
For rooms with great historical significance or a high value concentration, e.g.
museums, churches, libraries.
For rooms where cabling is unwanted for aesthetic reasons.
For rooms in which reconstruction work is permanently or regularly carried out,
e.g. exhibition halls.
FDnet
SMF6120
DOW1171