Chilled Water Recycle Mode; Safety Shutdown; Before Initial Start-Up; Job Data Required - Carrier 23xl Start-Up, Operation And Maintenance Instructions Manual

Hermetic screw liquid chillers with hcfc-22 and hfc-134a, 50/60 hertzpic ii controls
Hide thumbs Also See for 23xl:
Table of Contents

Advertisement

The soft stop amps threshold function can be terminated and
the compressor motor deenergized immediately by depressing
the STOP button twice.
Chilled Water Recycle Mode —
cycle off and wait until the load increases to restart when the
compressor is running in a lightly loaded condition. This cy-
cling is normal and is known as "recycle." A recycle shutdown
is initiated when any of the following conditions are true:
• the chiller is in LCW control, the difference between the
LEAVING CHILLED WATER temperature and ENTER-
ING CHILLED WATER temperature is less than the
RECYCLE SHUTDOWN DELTA T (found in the
SETUP1 table) and the LEAVING CHILLED WATER
temperature is below the CONTROL POINT, –5 F
(–15.0 C) the CONTROL POINT has not increased in the
last 5 minutes and ICE BUILD is not active.
• the ECW CONTROL OPTION is enabled, the difference
between the ENTERING CHILLED WATER temperature
and the LEAVING CHILLED WATER temperature is less
than the RECYCLE SHUTDOWN DELTA T (found in
the SETUP1 table), and the ENTERING CHILLED
WATER temperature is below the CONTROL POINT
–5 F (–15.0 C) and the CONTROL POINT has not
increased in the last 5 minutes.
• the LEAVING CHILLED WATER temperature is within
3º F (2º C) of the EVAP REFRIG TRIPPOINT.
When the chiller is in RECYCLE mode, the chilled water
pump relay remains energized so the chilled water temper-
ature can be monitored for increasing load. The recycle control
uses RECYCLE RESTART DELTA T to check when the com-
pressor should be restarted. This is an operator-configured
function which defaults to 5º F (3º C). This value can be
viewed or modified on the SETUP1 table. The compressor will
restart when the chiller is:
• in LCW CONTROL and the LEAVING CHILLED
WATER temperature is greater than the CONTROL
POINT plus the RECYCLE RESTART DELTA T.
• in ECW CONTROL and the ENTERING CHILLED
WATER temperature is greater than the CONTROL
POINT plus the RECYCLE RESTART DELTA T.
Once these conditions are met, the compressor initiates a
start-up with a normal start-up sequence.
An alert condition may be generated if 5 or more recycle
start-ups occur in less than 4 hours. Excessive recycling can re-
duce chiller life; therefore, compressor recycling due to ex-
tremely low loads should be reduced.
To reduce compressor recycling, use the time schedule to
shut the chiller down during known low load operation period,
or increase the chiller load by running the fan systems. If the
hot gas bypass is installed, adjust the values to ensure that hot
gas is energized during light load conditions. Increase the
RECYCLE RESTART DELTA T on the SETUP1 table to
lengthen the time between restarts.
The chiller should not be operated below design minimum
load without a hot gas bypass installed.
Safety Shutdown —
A safety shutdown is identical to a
manual shutdown with the exception that, during a safety
shutdown, the CVC displays the reason for the shutdown, the
alarm light blinks continuously, and the spare alarm contacts
are energized.
After a safety shutdown, the
pressed to clear the alarm. If the alarm condition is still present,
the alarm light continues to blink. Once the alarm is cleared,
the operator must press the
CCN
start the chiller.
The
chiller
may
softkey must be
RESET
or
softkeys to re-
LOCAL

BEFORE INITIAL START-UP

Job Data Required

list of applicable design temperatures and pressures
(product data submittal)
chiller certified prints
starting equipment details and wiring diagrams
diagrams and instructions for special controls or options
23XL Installation Instructions
pumpout unit instructions

Equipment Required

mechanic's tools (refrigeration)
digital volt-ohmmeter (DVM)
clamp-on ammeter
electronic leak detector
absolute pressure manometer or wet-bulb vacuum indi-
cator (Fig. 30)
500-v insulation tester (megohmmeter) for compressor
motors with nameplate voltage of 600 v or less, or a
5000-v insulation tester for compressor motor rated
above 600 v
Using the Optional Storage Tank and Pump-
out System —
Refer to Chillers with Storage Tanks sec-
tion, page 71 for pumpout system preparation, refrigerant
transfer, and chiller evacuation.
Remove Shipping Packaging —
aging material from the control center, power panel, motor
cooling and oil reclaim solenoids, motor and bearing tempera-
ture sensor covers, and the factory-mounted starter.
Open Oil Circuit Valves —
ter isolation valves (Fig. 3 and 4) are open by removing the
valve cap and checking the valve stem.
Tighten All Gasketed Joints —
ly relax by the time the chiller arrives at the jobsite. Tighten all
gasketed joints to ensure a leak-tight chiller.
Check Chiller Tightness —
proper sequence and procedures for leak testing.
23XL chillers are shipped with a full refrigerant and oil
charge. Units may be ordered with the refrigerant shipped sepa-
rately, and a 15 psig (103 kPa) nitrogen-holding charge in each
vessel. To determine if there are any leaks, the chiller should be
charged with a refrigerant tracer. Use an electronic leak detec-
tor to check all flanges and solder joints after the chiller is
pressurized. If any leaks are detected, follow the leak test
procedure.
If the chiller is spring isolated, keep all springs blocked in
both directions to prevent possible piping stress and dam-age
during the transfer of refrigerant from vessel to vessel during
the leak test process, or any time refrigerant is being trans-
ferred. Adjust the springs when the refrigerant is in operating
condition and the water circuits are full.
Refrigerant Tracer —
environmentally acceptable refrigerant tracer for leak testing
with an electronic detector or halide torch.
Ultrasonic leak detectors can also be used if the chiller is
under pressure.
Do not use air or oxygen as a means of pressurizing
the chiller. Mixtures of HFC-134a and air can undergo
combustion.
49
Remove any pack-
Check to ensure the oil fil-
Gaskets normal-
Figure 31 outlines the
Carrier recommends the use of an

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents