Haier CI0193AANB Installation, Operation And Technical Manual page 47

Air cooled semi-hermetic screw chiller
Table of Contents

Advertisement

Press 【Select mode】 button, turn to "unit operation select";
Press 【startup】 button, the middle of screen will appear "confirm" figure, press and then the chiller
will startup.
Press 【cooling】 button, the button will changed to black and turn to "cooling mode";
Press 【heating】 button, the button will changed to black and turn to "heating mode";
The 【local】button display the current control status, turn to 【remote】button after touching;
Individual control is means single compressor chiller or multi-chiller main control mode.
There is "second-class parameter setting" in the touch screen, which is only used by manufacturer,
if the chiller can not work normally, please contact with the dealer for help.
11.2.3 System control function
11.2.3.1 Cooling type
Press the 【Start】 button on the "start/stop chiller" display of touch screen, the cycling water
pump starts firstly, 2 minutes later fan motor starts and 1 minute later compressor startup.
Stop chiller directly: Press the 【Stop】 button on the "start/stop chiller" display of touch screen,
confirm and then stop is available. The master unit stops firstly, after the compressor stops, 3 minutes
later cycling pump will stop.
Upload procedure
48
HAIER CHILLER

Advertisement

Table of Contents
loading

Table of Contents