Components

Valve Combination
The valve combination is mounted on the domestic water
circuit. It is purpose is to mix the hot water with cold before
it reaches the water taps. This is to avoid burns, and to keep
the taps and seals from being destroyed by to hot water.
NOTICE!
Piping
Normally, copper piping is used for installing these systems.
Piping between boiler and accumulators should not be less
Remember to insulate all of the
35mm. If the piping is longer than 6 meters to the first tank
pipes in the boiler room.
it´s recommended to use 42mm.
The Accumulator Tank
Effecta Lambda must always be connected to some sort of
accumulator tank, where the energy is stored, and where the
domestic water and the hot water to the radiators is taken.
The accumulator is described more thorough on page 13.
The Draft Stabiliser
If you have a tall and wide chimney, it is possible that you
have to install a draft stabiliser. You might notice that you
have an irregular combustion, puffing sounds from the boiler.
This happens when the chimney sucks too much air through
the boiler. The placement of the draft stabiliser in the chimney
should be approx. one meter above the connection to the
boiler. This is because you have an overpressure from the
fan, and if you place the draft stabiliser too close to the boiler
you might have smoke coming out of the stabiliser.