Function blocks for gamma/L and Sigmas
Statistical range of the instance block 1
Variable
stat_Max_Freq
Status.Error
Status.Warnings
Status.Intake
Status.Auxiliary
Status.Pause
Status.Stop
Status.Flow
Status.FlowActive
Status.FactorDivider
Status.BatchMemory
Status.Unit
Status.Calibrated
Status.PBWD
Flags of the function block
Flag name
iiCycleWarning
iiCycleFault
iiCycleFaultPB
iiWorkaround
iiWorkaround2
Name of the error messages of the func‐
tion block
Name of the error messages
Errors.Minimum
Errors.AnalogError
Errors.FlowMonitoring
Errors.FailureDiaphragm
44
Type
Description
Real
Get maximum frequency via profibus of the pump. Con‐
version of the number into the real format
Bool
Errors are present.
Bool
Warnings are present.
Bool
Pump is in intake operation (higher-level function - see
metering pump operating manual)
Bool
Pump is in auxiliary mode (higher-level function)
Bool
Pump is switched to pause (higher-level function)
Bool
Pump is stopped
Bool
1 = Metering monitor present
Bool
1 = Metering monitor activated
Bool
1 =1/100, 0=1/1
Bool
1 = Batch memory is activated
Bool
1 = Gallons, 0 = Litres
Bool
1 = Pump is calibrated
Bool
1 (always)
Type
Description
Int
Flag - for how many cycle has the warning already been
queued. If this counter is > iiCycle_Error, then oxWarning
will be set
Int
Flag - for how many cycle has the fault has already been
queued. If this counter is > iiCycle_Error, then oxError will
be set
Int
Flag - for how many cycle has the fault Profibus already
been queued. If this counter is > iiCycle_Error, then oxEr‐
rorProfibus will be set
Int
Internal use for workaround
Int
Internal use for workaround
Type
Description
Bool
0 = No error,
1 = Level of metering medium too low
Bool
0 = No error,
1 = Analog error
Bool
0 = No error,
1 = Error metering monitor
Bool
0 = No error,
1 = Diaphragm break

Hide quick links: