Boilers For Following Countries: Germany, Austria, Czech Republic, Slovenia - DeDietrich GT 330 Installation And Service Manual

Fuel oil/gas-fired boiler
Hide thumbs Also See for GT 330:
Table of Contents

Advertisement

3.3.3

Boilers for following countries: Germany, Austria, Czech Republic, Slovenia

Conditions of use:
Maximum operating temperature: 100 °C
Maximum operating pressure: 6 bar
Thermostat adjustable from 30 to 90°C
Safety thermostat: 110 °C
Boiler
Useful output
Power input
Water content
Number of sections
Number of baffle plates
Maintenance consumption (A)
Water resistance
Flue gas temperature (C)
Pressure in the furnace for nozzle pressure = 0
(C) (D)
Mass flue gas flow rate (C)
DIN 4705 Teil 1
Combustion chamber
Weight (empty)
In order for the boiler to operate correctly, it is imperative
to respect the draught at the nozzle: 0 at the nozzle.
(A)
Standby consumption LVR 92
(Boiler temperature: 70 °C)
(B)
1 mbar = 10 mmWG = 10 daPa.
(C)
Nominal operation (top boiler power).
(D)
In no event must the draught at the nozzle exceed 0.2 mbar.
05/03/2013 - 300007650-001-02
kW
kW
l
∆ T = 30K
%
mbar
∆ T = 10K (C)
(B)
mbar
∆ T = 20K (C)
(B)
°C
Pa
(B)
kg per
Fuel oil
sec
kg per
Natural gas
sec
Inscribed diameter mm
Length
mm
3
Volume
m
kg
Test conditions:
CO
Fuel oil = 13%
²
CO
Natural gas = 9.5%
²
Ambient temperature: 20 °C
GT 334
GT 335
GT 336
55-80
80-110
110-140
60-87
86-120
119-153
96
116
136
4
5
6
10
0.150
0.135
0.125
8.7
16.5
2.1
3.8
< 180
< 180
< 180
20
35
0.037
0.051
0.065
0.039
0.054
0.068
377
377
377
571
731
891
0.096
0.122
0.148
612
736
846
GT 330
3. Technical description
GT 337
GT 338
140-175
175-210
151-190
188-228
156
176
6
7
8
10
10
12
0.115
0.100
27
41.2
56.9
7
9.6
14.2
< 180
< 180
60
110
150
0.081
0.097
0.085
0.102
377
377
1051
1211
0.174
0.200
981
1103
GT 339
210-250
226-271
196
9
12
0.085
84
20.8
< 180
200
0.115
0.121
377
1371
0.226
1230
13

Hide quick links: