Input terminal board status (FD06, FE06)
Input terminal board status (current status): "Communication Number FD06"
Input terminal board status (status immediately before the occurrence of a trip): "Communication
Number FE06"
Using terminal function selection parameters, functions can be assigned individually to the terminals
on the input terminal board.
If a terminal function selection parameter is set to 0 (no function assigned), turning on or off the
corresponding terminal does not affect the operation of the inverter, so that you can use the termi-
nal as you choose.
When using a terminal as a monitoring terminal, check beforehand the function assigned to each
terminal.
Data composition of input terminal board status (FD06, FE06)
Bit
Terminal name
0
F
1
R
2
S1
3
S2
4
VI *1
5 to15
(Reserved)
*1:VI function when F109 is 2:logic input.
Example: Data set for FE06 when the F and S1 terminals are ON = 0005H
FE06:
Function (parameter title)
Input terminal function selection 1 (f111)
Input terminal function selection 2 (f112)
Input terminal function selection 2 (f113)
Input terminal function selection 4 (f114)
Input terminal function selection 5 (f115)
---
BIT15
0
0
0
0
0
0
0
0
0
47
bit0
0
0
0
0
0
0
1
0
5
0
E6581657
0
1
OFF
ON
---
---
1