7. Commands and monitoring from the computer

Across the network, instructions (commands and frequency) can be sent to each inverter and the
operating status of each inverter can be monitored.

7.1. Communication commands (commands from the computer)

Communication command1
Commands can be executed on inverter frequencies and operation stop through communication.
The VF-nC3 series can enable command and frequency settings through communication irrespec-
tive of settings of the command mode selection (cmod) and frequency setting mode selection 1
(fmod). However, if "48 (49): Forced switching from communication to local is set by input ter-
minal function selection (f11o to f115), a change to a command other than communication
and to a frequency command is feasible through a contact on the terminal board.
Once the communication command (FA00) is set to enable communication command priority and
frequency priority, both priorities will be enabled unless OFF is set, power is turned off or is reset, or
factory default setting (typ) is selected. Emergency stop is always enabled even though com-
munication command priority is not set.
Table 1 Data construction of communication commands (communication number: FA00)
bit Specifications
0
Preset speed operation fre-
quencies 1
1
Preset speed operation fre-
quencies 2
2
Preset speed operation fre-
quencies 3
3
Preset speed operation fre-
quencies 4
4
Motor selection (1 or 2) (THR
2 selection)
5
PI D control
6
Acceleration/deceleration
pattern selection (1 or 2)
(AD2 selection)
7
DC braking
8
Jog run
9
Forward/reverse run selec-
tion
10 Run/stop
11 Coast stop command
12 Emergency stop
13 Fault reset
14 Frequency priority selection
15 Command priority selection
Ex.: Forward run command used in two-wire RS485 communication (PFA008400) CR
1 is specified for bit 15 (communication command: enabled) and bit 10 (operation command).
FA00:
Ex.: Reverse run command used in two-wire RS485 communication (PFA008600) CR, (PFA00C600) CR
8600H : To disable frequency instructions from the computer
C600H : To enable also frequency instructions from the computer
(Communication Number : FA00,FA04)
0
Preset speed operation is disabled or preset
speed operation frequencies (1-15) are set
by specifying bits for preset speed operation
frequencies 1-4.
(0000: Preset speed operation OFF,
001-1111: Setting of preset speed opera-
tion frequencies (1-15))
Motor 1
(THR 1)
Normal operation
Accelera-
tion/deceleration pat-
tion/deceleration pat-
tern 1 (AD1)
tern 2 (AD2)
OFF
Forced DC braking
OFF
Forward run
Reverse run
Stop
Standby
OFF
Emergency stop
OFF
OFF
OFF
BIT15
1
0
0
0
0
1
0
4
8
43
1
Motor2
THR1 : pt=setting value,
(THR2)
vl, vlv, vb, thr
THR2 :pt=0, f170,
f171, f172, f173
PI D OFF
Accelera-
AD1 : acc, dec
AD2 : f500, f501
Jog run
Run
Coast stop
Always enabled, "E" trip
Reset
No data is returned from the inverter.
Enabled
Enabled regardless of the setting
of fmod
Enabled
Enabled regardless of the setting
of cmod
BIT0
0
0
0
0
0
0
0
0
0
0
E6581657
Remarks
0