Terminal board output data (FA50)
The output terminal board on each inverter can be directly controlled with the computer.
To use this function, select functions 92,93 in advance for the output terminal function selection
parameters f130、f132. If bit 0 through bit 6 of terminal board output data (FA50) are set with
the computer, data specified (0 or 1) can be sent to any output terminal.
Data composition of terminal board output data (FA50)
Bit
0
(Output terminal no.: 92, 93)
1
2
3
4
5
6
7
Example of use: To control only the OUT terminal with the computer
To turn on the OUT terminal, set the output terminal function selection 1 parameter (f130)
to 92 (output terminal function selection (positive logic)) and specify 01H for FA50.
FA50:
FM analog output (FA51)
The FM analog terminal on each inverter can be directly controlled with the computer.
To use this function, set the FM terminal meter selection parameter (fmsl) to 18 (communication
data output).
This makes it possible to send out the data specified as FM analog output data (FA51) through the
FM analog output terminal. Data can be adjusted in a range of 0 to 100.0 (resolution of 8 bits).
For details, refer to "Meter setting and adjustment" of the instruction manual included with the in-
verter.
Information for reset or not (FA87)
FA87 sets to '1' by user-communication. If the inveter reset, FA80 set to '0' by the inverter.
Output terminal function
Specified data output 1
(Reserved)
(Reserved)
(Reserved)
(Reserved)
(Reserved)
(Reserved)
(Reserved)
BIT7
0
0
0
0
0
0
45
0
OFF
BIT0
0
0
1
1
E6581657
1
ON