Toshiba TOSVERT VF-nC3 Instruction Manual page 12

Hide thumbs Also See for TOSVERT VF-nC3:
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
Inverter → computer (binary mode)
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched.
This is because there will be a risk that the returned data may be deformed.
• Data returned when data is processed normally (Binary mode)
Omissible
(3.5bytes
"/"
INV-NO
Blank)
(2FH)
1 byte
1. 2FH ("/") (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number... 00H to 3FH (The inverter number is omitted if it is not found in the data
3. CMD (1 byte)
4. Communication No. (4 bytes)
5. Data (2 bytes)
6. Sum (1 bytes)
CMD
Communication No.
1 byte
2 bytes
Checksum area
received.)
If the inverter number matches up with that specified from the operation panel, data will be
returned from the inverter. If the inverter number does not match, the data will be invalid
and no data will be returned.
: Command...The command is also used for a check when the inverter is tripped.
Under normal conditions...52H (R), 47H (G), 57H (W) or 50H (P) is returned, depending on
the command received.
When the inverter is tripped...The lowercase letter 72H (r), 67H (g), 77H (w) or 70H (p) is
returned with 20H added to it, depending on the command received.
: The communication number received is returned.
: Data ... 0000H to FFFFH
The data read is returned for the 52H (R) and 47H (G) commands, while the data written is
returned for the 57H (W) and 50H (P) commands.
: Checksum (not omissible) 00H to FFH
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start
code to the data.
DATA
2 bytes
Not omissible
11
E6581657
SUM
(3.5bytes
1 byte
Blank)

Hide quick links: