efesotomasyon.com -Toshiba inverter,drive,servo,plc
Communication command2
This command is enabled only when the communication command is enabled. Set Bit 15 of
Communication Command 1 (communication Number: FA00) to "1" (enable). When enabling the
communication command by Communication Command 1, commands by communication can be
given the priority irrespective of the setting of the command mode selection parameter (cm0d).
However, if "48 (49): Forced switching from communication to local is set by input terminal function
selection (f11o to f115), the enabled command and frequency will be given the priority.
Once enabled, this setting will be enabled till disable is set (0 setting), power is turned off or is reset,
or factory default setting (typ) is selected.
Table 2 Data construction of communication command 2 (FA20)
Bit
0
(Reserved)
1
(Reserved)
2
(Reserved)
3
(Reserved)
4
(Reserved)
5
(Reserved)
6
(Reserved)
Maximum
7
forced stop
8
(Reserved)
9
(Reserved)
10
(Reserved)
11
(Reserved)
12
OC stall level swich
13
(Reserved)
14
(Reserved)
15
(Reserved)
Frequency setting from the computer
Setting range: 0 to maximum frequency (fh)
This frequency command is enabled only when the frequency command by communication is en-
abled. To make frequency commands from the computer valid, set the frequency setting mode se-
lection parameter (fmod) to RS485 communication (communication No. 0004: 3 (RS485 com-
munication input) or select the "Command priority" option (bit 14 of FA00 : 1 (enabled)). In this case,
frequency commands by communication will be enabled independent of fmod setting.
However, enabled commands and frequencies are given the priority if "48 (49): Forced switching
from communication to local," is set by input terminal function selection (f11o to f115).
Once enabled, this frequency setting will be enabled till disable is set (0 setting), power is turned off
or is reset, or factory default setting (typ) is selected.
Set a frequency by communication hexadecimal in Communication Number FA01. (1=0.01Hz (unit))
Example: Operation frequency 80Hz command RS485 communication (PFA011F40)
80Hz=80÷0.01=8000=1F40H
(Communication Number : FA20)
Function
0
-
-
-
-
-
-
-
deceleration
Normal
-
-
-
-
OC satll 1
-
-
-
"Communication Number: FA01"
44
1
Remarks
-
-
-
-
-
-
-
Enabled
-
-
-
-
OC satll 2
-
-
-
CR
E6581657