Available languages
  • EN

Available languages

  • ENGLISH, page 1
Accuracy
Refer to "Specifications" for operating conditions and temperature coefficient.
Accuracy is specified as follows: ± (a percentage of the reading + a fixed amount) at
18 °C to 28 °C (64 °F to 82 °F), 0% to 80% relative humidity
AC Current
Range
400.0 A
60.0 to 400.0 A
1000 A
400 to 1000 A
* ± (1.5% + 0.7 A) for CM-1550.
** ± (1.9% + 0.7 A) for CM-1550.
± 1.0% position error
AC Voltage
Range
400.0 V
± (1.0% + 0.5 V)*
750 V
± (1.0% + 5 V)
* Below 60.0 V, accuracy is ± (1.0% + 0.7 V) for CM-1550.
CM-1500 is average sensing, RMS calibrated.
CM-1550 is true RMS sensing. Accuracy is specified for sine waves at full scale and non-sine
waves below half scale. For non-sine waves, add the following crest factor corrections:
• Crest factor 1.4 to 2.0, add 1.0%
• Crest factor 2.0 to 2.5, add 2.5%
• Crest factor 2.5 to 3.0, add 4.0%
Maximum crest factor is 2 at 600 A or 600 V, and 1.5 at 1000 A or 750 V.
Input Value
0.0 to 60.0 A
Accuracy
Accuracy (50 to 60 Hz)
± (1.5% + 0.5 A)*
± (1.5% + 0.5 A)
± (1.9% + 7 A)
Frequency Response
50 to 500 Hz
CM-1500 • CM-1550
Accuracy (61 to 400 Hz)
± (1.9% + 0.5 A)**
± (1.9% + 0.5 A)
± (2.5% + 7 A)
Input Impedance
1 MΩ || < 100 pF
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cm-1550