Diesel generating set
Table of Contents

Advertisement

2. Modified coefficient table of ambient condition power
The conditions of generator rated output:
Altitude: 0 m
Ambient temperature: 25
Ambient modified coefficient: C (Relative humidity 30%)
Ambient temperature ( )
Altitude
(m)
25
30
0
1
0.98
500
0.93
0.91
1000
0.87
0.85
2000
0.75
0.73
3000
0.64
0.62
4000
0.54
0.52
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
temperature is 35
, relative humidity is 80%, the rated power of generator is:
P=P
(C-0.02) = 5
(0.82-0.02) = 4KW
N
Relative humidity: 30%
35
40
45
0.96
0.93
0.90
0.89
0.87
0.84
0.82
0.80
0.78
0.71
0.69
0.66
0.6
0.58
0.56
0.5
0.48
0.46