Toshiba RAS-B10EKVP-E Service Manual page 101

Split type
Hide thumbs Also See for RAS-B10EKVP-E:

Advertisement

Ilmalämpöpumppujen myynti, huolto ja asennus: Jäähdytinpalvelu RefGroup Oy.
No.
Part name
TE sensor
• Attachment
11
(outdoor heat
With the leads pointing downward and the sensor
exchanging
leads pointing in the direction shown in the figure,
temperature
install the sensor onto the straight pipe part of the
sensor)
condenser output pipe.
TS sensor
• Attachment
12
(intake
With its leads pointing
temperature
downward, point the
sensor)
sensor in the direction
of the packed valve,
and install it onto the
straight pipe part of
the intake pipe.
TD sensor
• Attachment
13
(outlet
With its leads pointed
temperature
downward, install the
sensor)
sensor onto the
vertical straight pipe
part of the outlet pipe.
TO sensor
• Attachment
14
(outside air
Insert the outdoor air temperature sensor into the
temperature
holder, and install the holder onto the heat
sensor)
exchanger.
Lue lisää nettisivuiltamme: www.ilmalämpöpumput.com
Procedures
Detail C for 13, 16EAVP-E
Detail C for 10EAVP-E
– 101 –
Detail B
• Shown in the above figure is
the model 13EAVP-E.
• The sensor mounting positions
in the model 10EAVP-E are all
the same with the sole excep-
tion of the TE sensor. Refer to
the figure shown on the left.
CAUTION
During the installation work
(and on its completion), take
Detail B
care not to damage the
coverings of the sensor
leads on the edges of the
metal plates or other parts.
It is dangerous for these
coverings to be damaged
since damage may cause
electric shocks and/or a fire.
CAUTION
After replacing the parts,
check whether the positions
where the sensors were
Detail A
installed are the proper
positions as instructed. The
product will not be controlled
properly and trouble will
result if the sensors have not
been installed in their proper
positions.
Arrow D
Remarks
Detail A
Arrow D
Detail C