Bosch RFRC-OPT Reference Manual page 43

Hide thumbs Also See for RFRC-OPT:
Table of Contents

Advertisement

RADION receiver OP
Figure 13.1: Remove the detector cap
4.
Figure 13.2: Remove the detector cap
1   Optical base
2   Optical chamber
3   Alarm cap
5.
6.
7.
8.
9.
10. Test the detector's sensitivity.
Bosch Security Systems, Inc.
Squeeze the optical chamber where indicated and pull it up and away from the detector.
1
2
3
Use compressed air or a soft-bristled brush to remove dust and dirt from the smoke
chamber base.
Align the optical chamber with the base and snap down into place.
To attach the detector cap, line the cap up with the detector, press the cap onto the
detector, and turn clockwise to snap it firmly into place.
Observing the proper polarity, install the batteries and the battery cover. If the batteries
are not installed properly, the detector will not fit onto the mounting base. Ensure that
the batteries are properly installed.
Mount the detector onto the mounting base.
Reference Guide
RADION smoke | en
43
2014.12 | 02 | F.01U.261.835