16
en | RADION receiver OP
Trouble state:
The receiver enters a trouble state when an internal self-test detects a failure. Another cause
for the receiver entering into a trouble state would be if the receiver detects radio frequency
interference failure.
LED condition
Continuous fast flash: A continuous pulse
between On and Off states (Trouble state)
Maintenance state
The receiver enters a maintenance state when the address switch settings are set between
switch 5 – switch 8.
LED condition
Continuous Flash: A continuous pattern of
short off time, followed by long on time.
Off state
Indicates there is a power failure to the receiver. Check the wire connections for proper
wiring.
3.5
Specifications (RFRC-OPT)
Housing Dimensions (H x W x D)
Power/Voltage
Maximum Current Draw
Operating Environment
Relative Humidity
Frequency
Wiring Distance
Wiring Gauge
Wall and Cover Tamper Switch
Tab. 3.3: RFRC-OPT Specifications
2014.12 | 02 | F.01U.261.835
State description
–
Indicates the receiver is in a trouble
state, experiencing a radio frequency
interference failure
–
A communication failure with internal
hardware components within the
receiver
State description
Indicates the receiver is in Maintenance
Mode.
139.7 mm x 209.6 mm x 31.8 mm (5.5 in x
8.25 in x 1.25 in)
12 VDC nominal
100 mA
Functional range: -10°C to +49°C (+14°F to
+120°F)
EN 50130-5 Class II only: -10 C to 40 C (+14 F
to +104 F
Up to 93% non-condensing
433.42 MHz
Maximum distance of 300 m (1000 ft) from
the control panel
0.65 mm (22 AWG) to 1.3 mm (16 AWG)
maximum
–
Transmits a tamper signal when the
device is removed from its base or
pulled away from the wall
Reference Guide
RADION receiver OP
Bosch Security Systems, Inc.