Blower Packs Troubleshooting; Procedure; Digital On/Off Humidistat Sensor Calibration - Nortec NH Series Installation Manual

Nh series electrode steam humidifier
Hide thumbs Also See for NH Series:
Table of Contents

Advertisement

(2) If the SAM-e is condensing inside the duct, make sure that the design conditions have
not changed.
(3) If grommets leak, make sure the tubes are firmly inserted, if cracks or damage are
found, replace grommet.

4. BLOWER PACKS TROUBLESHOOTING

A. PROCEDURE
(1) An optional blower pack (BP), ensure power supplied to blower pack either from
humidifier or other source, if present, gets its primary voltage from inside the humidifier.
This way, only one external power source has to be connected to the equipment.
Confirm this power source before troubleshooting the blower pack.
(2) Ensure blower pack is installed per Chapter 10-10 Installation.
(3) If fans are not functioning, confirm safety is not open. Fans are only ON when steam is
being discharged.

5. DIGITAL ON/OFF HUMIDISTAT SENSOR CALIBRATION

A. PROCEDURE
(1) The humidity sensor is factory calibrated, however, it can be field recalibrated.
(a) The calibration routine can be accessed by pressing and holding down the option
button for five seconds. A new screen will appear with the calibration adjustments.
(b) Press the up
(c) To adjust the calibration press the Option
display the current calibration trim. The calibration trim can be adjusted by
pressing the up or down buttons to the desired level and then pressing the option
button to confirm the settings.
(d) Press the Power
A properly calibrated hygrometer should be used in conjunction with any calibration

procedure.

10-40
Page 59
2008-08-28
or down
buttons until the text calH appears on the LCD screen.
button to return to the normal display.
NOTE
button. The screen should load to