Nh Electrode Steam Humidifiers; Maintenance; When To Replace The Steam Cylinder; Extended Shut-Down - Nortec NH Series Installation Manual

Nh series electrode steam humidifier
Hide thumbs Also See for NH Series:
Table of Contents

Advertisement

1. NH ELECTRODE STEAM HUMIDIFIERS

Typical tools required for any maintenance procedure:
- Slotted Screwdriver
- Small Slotted Screwdriver
- Phillips Screwdriver
- Needle-Nose Pliers
- Wrench
A. MAINTENANCE
THE PLUMBING AND ELECTRICAL COMPARTMENTS CONTAIN HIGH
VOLTAGE COMPONENTS AND WIRING. ACCESS SHOULD BE
LIMITED TO AUTHORIZED PERSONNEL ONLY.
(1) The NHTC and its components are a very low maintenance system. The only
maintenance normally required is to change the cylinder, clean out the drain valve
assembly, clean out the inlet valve screen and know the procedure for extended shut-
down and start-up.
B. WHEN TO REPLACE THE STEAM CYLINDER
(1) The steam cylinder is disposable and must be replaced at end of cylinder life. Cylinder
life is dependent on water supply conditions and humidifier usage. Failure to replace
the cylinder at the end of cylinder life will cause the unit to lock out. NORTEC is not
responsible for any damages resulting from, or attributed to, the failure to replace a
spent cylinder (see Manufacturer's Warranty). There are many indications, each of
which signifies the end of cylinder life. See 10-20 Operation, Table 4, for details on how
the unit functions and determines end of cylinder life.
C. EXTENDED SHUT-DOWN
(1) As long as the NHTC is powered, it will automatically drain the cylinder when there has
not been a call for humidity for an extended period of time. This feature will reduce or
prevent the possibility of corrosion of the electrodes and the accumulation of algae and
bacteria growing in the cylinder. The cylinder will remain empty until there is a call for
humidity at which time the fill valve will open and refill the cylinder. The unit will go
through its normal process for optimum operation.
(2) Should it be required to disconnect power to the humidifier for a period of extended
shut-down, always drain the cylinder first. Leave the switch in the OFF position and
'open' the main external fused disconnect to stop power to the humidifier. Close the
shut-off valve in the water supply line feeding the humidifier.
MAINTENANCE PROCEDURES
WARNING
DISCONNECT MAIN POWER BEFORE ANY SERVICING.
WARNING
10-30
Page 50
2008-08-28