Table 4. Recommended Condensate Line at Distributor(s)
Dispersion Method
1 x Steam Distributor
3 x Steam Distributor
Note: *When using more then 1 steam distributor, the condensate line must be trapped before it is
joined together. See figure 4
Table 5. Equivalent Lengths of Elbows and Tee Fittings
Nominal Tube
Diameter
0.750 / 0.875 in.
1.500 / 1.750 in.
2.000 / 2.500 in.
Humidifier
NH 5-30
NH 50-100
NH 150-200
NOTE: * SAM-e may have multiple 1.75 in. inlets depending on order.
** mini SAM-e inlet is determined on order and may have two 1.75 in. OD inlets.
10-10
Page 17
2008-08-28
Condensate Hose
0.375 inch
NORTEC 132-8840
0.375 inch
NORTEC 132-8840
Standard 90degree
Elbow
2 ft.
3 ft. 6 in.
4 ft. 6 in.
Table 6. Humidifier and Distributor Inlet/Outlet Sizes
Steam Outlet
0.875 in. OD
1.75 in. OD
Two 1.75 in. OD
Copper Tube (Potable)
0.250 inch. MED-L Tubing
(0.375 inch OD)
0.500 inch. MED-L Tubing
(0.875 inch OD)
Standard 45 degree
Elbow
1 ft.
1ft. 9 in.
2 ft. 3 in.
Distributor
ASD, BSD
CSD
Blower Pack
SAM-e
mini SAM-e
Stainless Steel Tube
(RO or DI)
0.375 Tube 0.049 inch thick
0.650 Tube 0.049 inch thick
Side Outlet Tee
4 ft.
7 ft.
10 ft.
Steam Inlet
0.875 inch OD
1.75 inch OD
0.875 inch OD or
1.75 inch OD
1.75 inch OD*
0.875 or 1.75 inch OD**