Humidifier Mandatory Pre-Start-up Checklist (p.1 of 2)
Unit Serial #: _ _ _ _ _ _ _ _
Unit type: NHSC / NHDI
Customer/Job:_______________ Address: __________________________________________________
Inspected by: _____________
______________________________________________________________________________________________
WATER QUALITY:
W
r
- Well water
- Conductivity: _______mhmos
HUMIDIFIER MOUNTING:
Clearances around the unit
- Front (door opens freely?)
- Top (steam lines)
- Bottom (fill, drain, controls)
- Right (main pwr)
- Left (main pwr)
- Ensure the scale tank bracket is locked in place
STEAM LINES:
- Slope up 2" per 12"
- Slope down ½" per 12"
r
- Traps
r
- Insulated
- Length/Size ____________
- 90 deg. elbows qty: ____
- Can condensate be trapped anywhere in the steam line? Yes
WATER LINES:
-½" at max 4ft from the unit
-water pressure: 30-80psig
DRAIN LINES:
-Air gap located within 3ft of the unit
WIRING:
No loose wires around the unit or on the PC board? Yes
CONTROLS:
- High limit:
- Air proving:
- Mod controller:
- Other:
POWER
- Voltage, amperage rating and fuse corresponds to Spec Label
- Disconnect switch located close to humidifier
Field contact:___________________________ Signature:_______________________________
NHSC / NHDI Electric Steam Humidifier
# of humidifiers: _____
Voltage: _____V/___ph
Date of inspection: ___/___/___
r
-City water
Acceptable
3ft min
1ft min
1ft min
3ft min
2" min
CONDENSATE LINES:
r
- Slopped back to drain
r
- Trapped 2" more than static duct pressure
- Size _______
- 45 deg. Elbows qty: ____
- 3/8" connection at fill
r
- Slopped to drain
Installed
Location / Wiring /Setting
r
_____________________
r
_____________________
r
_____________________
r
_____________________
Tag:_____________
Steam output: ____lbs./hr
r
-Softened water
- Hardness: _____gr.
Obstruction
r
_______________
r
____________________
r
____________________
r
____________________
r
____________________
r
r
r
no
r
-Size:________
r
r
no
r
r
–Silica____ppm
r
r