Installation; Receiving & Unpacking Equipment; Pre-Installation Checkpoint; Basic Humidifier Configuration - Nortec NHDI Installation & Operation Manual

Resistive element steam humidifiers installation, operation, maintenance, and troubleshooting guide
Hide thumbs Also See for NHDI:
Table of Contents

Advertisement

INSTALLATION

RECEIVING & UNPACKING EQUIPMENT
1. Check packing slip to ensure ALL material has
been delivered.
2. All material shortages are to be reported to
NORTEC within 48 hours from receipt of
goods. NORTEC assumes no responsibility
for any material shortages beyond this period.
3. Inspect shipping boxes for damage and note
on shipping waybill accordingly.
4. After unpacking, inspect equipment for
damage and if damage is found, notify the
shipper promptly.
5. All NORTEC products are shipped on an
F.O.B. factory basis. Any and all damage,
breakage or loss claims are to be made
directly to the shipping company.

PRE-INSTALLATION CHECKPOINT

1. Ensure that available voltage and phase
corresponds with humidifier voltage and phase
as indicated on humidifier's spec label (see
Figure #1).
2. Ensure that the dedicated external disconnect
is of sufficient size to handle the rated amps
Figure #1
NHSC / NHDI Series Humidifier
Steam Outlet
1.75" O.D.
Scale
Water
Collector
Supply
Tank
NOTE: NHDI does not have the scale collector tank.
Optional SSR
Cooling Fans
Keypad
Display
Power and
Spec
Control
Label
Wiring
Drain
Valve
- 1 -
as indicated on the spec label. Refer to local
codes.
3. Report any discrepancy immediately.

BASIC HUMIDIFIER CONFIGURATION

NORTEC NHSC / NHDI humidifiers share a
modular sheet metal cabinet. Each unit has a right
side electrical compartment. Each electrical
compartment has a hinge-down front door which is
removable from any partially or fully opened position.
Each electrical compartment has a screw-mounted
right side cover which can open for ease of electrical
connection. For safety, the door when closed keeps
the side cover from being opened.
Single units have a plumbing compartment
attached to the left side of the electrical. Double units
have a second plumbing compartment. Each
plumbing compartment has a hinge-down front door.
For safety, the door must be closed in order to engage
the safety interlock. To avoid any danger, never
operate the humidifier with a door off.
To open the doors, unlock, lift door up slightly and
pull top of door forward. Door will hinge 180 degrees
and hang straight down. To remove door, swing door
parallel to floor. Then lift up slightly and out. To
reinstall door, hold parallel to floor and insert hinge
pins at bottom.
Figure #2
Minimum Steam Line Clearance
Trap
* See Section On
Condensate
Return Line
NOTE: Trap must be 3' minimum down from steam distributor.
If not, condensate must be routed to drain.
Min. 10 Degree Slope
Min. 12"

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nhsc

Table of Contents