INTERROGATION OF THE OPERATING
STATUS
The NHSC / NHDI operating and display unit has
a "display menu" from which various operating
parameters can be viewed.
Note: It is not possible to change the values on the
display level.
Operation
Call up the display level with <ê> or <é>.
<ê> next operating parameter.
<é> previous operating parameter.
Exit the display level with <Menu>
Description of the operating parameters on the
display level
The following describes the individual operating
parameters that can be selected using the keys <ê>
and <é>, after the display level has been called up.
Steam Productions
steam-prod[%]
ref.=50/act=25
Current actual and nominal value of steam
production in percentage of total output.
Nominal value: Unit capacity x input signal value.
Actual value: max. Unit capacity x input signal
value x capacity limitation.
Note: If the internal controller is activated only the
actual value is shown.
Under the following conditions the actual value
may differ from the nominal value: upon activation of
the heating power, if capacity limitation is active during
the filling cycle of the steam cylinder.
Analog Input (humidity demand)
Analog input [%]
Current value of the signal applied to the analog
input in % of its max. value.
Note: If the internal controller is active the
displayed value corresponds to the current air humidity
(%rh).
25
Internal Controller
Internal controller activated ("on")/deactivated
("off")
Working Hours
Total of working hours elapsed since initial
commissioning of the steam humidifier.
Time Remaining to minor/major service
The time remaining (in hours) before the next
minor/major service.
Can be increased for poor water conditions or
decreased for good water conditions.
NHSC / NHDI Maintenance Intervals
- 14 -
Controller funct
off
elapsed time
623
time to mainten.
600/1200
Figure #17