Required pressures - Table 4. We recommend that the hot water distribution from the heater was as short
as possible to minimise heat losses.
Figure 4
2.4 ELECTRIC WIRING
Do not plug the water heater in HDO socket; it would not work properly in SMART
mode. The SMART mode (SMART HDO) will only work if 24/7 connected to power
supply.
2.4.1 ELECTRIC INSTALLATION GENERAL INFORMATION
In the electric wiring casing remove the partition corresponding with the input wire diameter of 8 or 10
(Figure 5). The degree of protection of electric parts of the heater is IP 44. Power input of electric element
is 2200 W.
U - Closure
P - Safety valve with
backflow valve
pressure of the
safety valve
M - Manometer
Z - Test valve
V - Drain valve
Table 4
Heaters must be provided with a discharge valve
mounted on the cold service water inlet to the
heater for potential disassembly or repair. When
assembling the security equipment, follow \u268
CSN 06 0830.
Allowable
operational
Start-up
overpressure
of the water
heater [MPa]
[MPa]
0,6
0,6
Maximum
pressure in the
cold water
pipes [MPa]
up to 0.48
- 12 -