5. PERFORMANCE DATA

5.1 Amendment coefficient of cooling capacity under different indoor/outdoor DB and WB temperature.
Indoor air inlet
temperature℃
DB
23
25
27
28
30
32
Actual cooling capacity calculation
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
— Nominal cooling capacity could be found from the performance parameters list;
— Amendment coefficient of cooling capacity could be found from table above.
5.2 Amendment coefficient of heating capacity under different indoor/outdoor DB and WB temperature.
Indoor air inlet DB
temperature ℃
Actual heating capacity calculation
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
Nominal heating capacity could be found from the performance parameters list
Amendment coefficient of heating capacity could be found from table above.
WB
25
16
0.98
18
1.05
19
1.1
20
1.12
22
1.19
24
1.26
-5
16
0.65
18
0.61
20
0.6
21
0.59
22
0.58
24
0.56
Outdoor air inlet DB temperature℃
30
35
0.94
0.89
1
0.95
1.05
1
1.07
1.02
1.13
1.08
1.20
1.15
Outdoor air inlet WB temperature ℃
0
6
0.80
1.02
0.76
1.02
0.75
1
0.72
0.99
0.71
0.97
0.7
0.96
PERFORMANCE DATA
40
43
0.85
0.82
0.90
0.87
0.95
0.91
0.96
0.93
1.02
0.99
1.08
1.05
10
15
1.13
-
1.12
-
1.11
1.25
1.1
1.24
1.09
1.23
1.08
1.22
7 | S e r v i c e M a n u a l