Airwell AWSI YIFA060–H13 Service Manual page 21

Table of Contents

Advertisement

Anti-cold air
a)Anti-cold air when the compressor is running
b) When TE is raising and TE<30℃, indoor fan stops, if 30℃≤TE<38℃, indoor fan runs at low wind speed.
c ) When TE≥38℃, indoor fan runs at setting speed
d) When TE is descending and TE>34℃, indoor fan runs at setting speed. When 28℃<TE≤34℃, indoor fan runs at low wind.
When TE ≤ 28℃, indoor fan stops.
a)Anti-cold air when the compressor is off
b) When TE>30℃,if indoor fan is originally on then it blows low wind( last for maximum 30S). c)When TE≤30℃, indoor fan stops.
Blowing surplus heat
When indoor temperature reach set temperature or turn off the unit , if TE>35℃, indoor fan motor operates at low wind, if
indoor temperature ≤35℃, indoor fan stops running.
Swing control
There are totally 4 swing modes: A, B, C, D, among them A and B is an assembly, C and D is an assembly. Each mode
switches through sleep button on remote control or wired control, detail operation
is as follows: press sleep button 10 times continuously in 5 second, buzzer sounds 4 times, and swing angle belongs to
C/D mode (it takes effect when repower on), in the same way press sleep button 10 times continuously in 5 second,
buzzer sounds 2 times, then swing returns to A/B mode (it takes effect when repower on). The swing mode switches
among assembly is accomplished by dip switch. Detailed operations are as follows: ON as A mode, OFF as B mode, OFF
as C mode.
CONTROL SYSTEM
20 | S e r v i c e M a n u a l