E N R O L L
1. At a system keypad, enter [ ][8][Installer's code].
2. Enter programming section [804].
3. Enter programming section [59] for keys assigned to partition 1, or [60] for keys assigned
to partition 2.
4. For each of the 4 function buttons, enter the 2-digit number of the function you want
to select. See the programming worksheets for a list of function key options.
5. Record your programming choices in the worksheets in the back of the manual.
6. To exit press [#].

3.4 Identified Wireless Keys

Reporting by the system of openings/closings by individual wireless keys and
command output [ ][7] activation by wireless key buttons may be supported on
certain control panels. To do this, the system will reserve access codes 17 – 32 for
wireless keys 01-16 respectively. You must program one access code for each wireless
key (using [ ][5] access code programming) for this feature to work correctly.
Refer to your system Installation Manual for information on access code programming.
Opening/Closing By Wireless Key Reporting
NOTES: The Identified Wireless Key Closing option is only available with the PC5010
v2.0, PC5020, PC5008 v2.0 and higher by turning section [015] option 4 off.
The Identified Wireless Key Opening option is only available with the PC1555 v2.1,
PC580 v2.1, PC5008 v2.1 and higher, PC5015 v2.2 and higher by turning Section [017]
Option 1 off.
To enable the reporting of closings by identified wireless keys:
• Make sure the control panel is v2.0 or higher
• Program a valid access code for each key
• Program a closing reporting code for each key's access code
• Disable the Quick Arm option in section [015] option [4]
To enable the reporting of openings by identified wireless keys:
• Make sure the control panel is v2.1 or higher
• Program a valid access code for each key
• Program an opening reporting code for each key's access code
• Enable the WLS Key Uses Access Codes by turning section [017] option [1] off.
Command Output Activation
NOTE: The Identified Wireless Key Command Output Activation feature is only available
with the PC5010, PC5020, PC5015, PC5008, PC1555 and PC580 v2.0 and higher.
To enable command output activation by wireless keys, do the following:
• Make sure the control panel is v2.0 or higher
• Program a valid access code for each key
• Enable the PGM output attribute Requires Access Code for each PGM output
programmed as [ ][7][1-4] in sections [141] to [154].
&
P R O G R A M
10
D E V I C E S