armed, these zones are delayed if a delayed zone
is violated first, or instant if this zone or an instant
zone is violated first.
• Silence Audible: A zone configured as Silence
Audible will, when activated, cause the panel to
shut off output PO3 and keypad sounders. When
this zone restores, the sounders will reactivate (if
the timeout has not expired). It is used to facilitate
voice communication for listen-in modules.
Keyswitch Toggle: Each time this zone is closed,
it will toggle the armed state of the panel. It has a
300 ms response time. No alarms or trouble
conditions are generated by a zone of this type.
Optionally, to support this feature, the panel will
generate a single siren beep for arm actions and a
double beep for disarm actions.
Note 1: If "Auto Bypass" is enabled (Address 10),
Keyswitch Toggle will force arm a "Not Ready"
zone.
Note 2: Zone 9 is pre-programmed as a Keyswitch
Toggle zone.
• Keyswitch On/Off: Not available when zone
doubling is used. When this zone is closed, it will
arm the panel. When it is shunted by an EOL
(supervised), the panel will be disarmed. No alarms
or trouble conditions will be generated by a zone of
this type. Opening the zone will not affect the
arming state of the control. When this option is
selected, keypads can not be used to arm or disarm
the system unless the keyswitch zone is manually
bypassed, prior to arming the system, from the
keypad. If the keyswitch zone is bypassed, any
keypad can perform all arming and disarming
functions.
Note: If "Auto Bypass" is enabled (Address 10),
Keyswitch On/Off will force arm a "Not Ready" zone.
• 24-Hour Fire with Verification: If a fire zone
alarms and it is programmed for verification, the
control will interrupt the programmable output(s) set
as a switched power return for 10 seconds. During
the 10 second power interruption, and for 15
seconds after power restoral, it will ignore all zone
status on all fire zones (to ignore inrush currents).
After fifteen seconds, it will monitor all fire zones for
two minutes. If any fire zone returns to alarm within
the two minute window it will create a fire alarm
condition. If a fire zone does not go into alarm
within the two minute window it will disregard the
initial trip. If another alarm occurs on a fire zone
with verification after the two minutes, it will start the
process over. After any fire zone is in alarm, all
subsequent fire zones are treated as instant (no
verification) until the next fire reset. This same
procedure will be performed when a [SYSTEM
RESET] is entered, except that the two minute
instant alarm monitoring period is not observed.
Since alarm and trouble reporting to the central
station for fire zones is the same as for burg zones
(i.e. it is based on the state of the zone) it is
possible for Fire, and Fire Trouble restoral signals to
DS7060-AUS Reference Guide
NOTE: The use of the controls fire alarm verification
• Fire: This zone is active and will alarm all 24 hours
NOTE: If force arming is enabled (see programming
• Interior Delayed: This is a zone programmed to be
• Day Monitor: This is a zone programmed to be a
Copyright © 1997-98 Detection Systems, Inc.
be transmitted even though the panel may still be
displaying these zone conditions. This is because
the displays are latched until cleared by an operator
action.
feature may not be permitted in some areas.
Check your local fire/building codes.
of the day regardless of the arming state of the
control. An alarm on a fire zone will be silenced by
entering a disarm code whether the control is
armed or not. If the fire zone restores and alarms
again the alarm will sound again. An open during
the armed or disarmed period will send a trouble
report and not an alarm. Fire zones are never silent,
invisible, or swinger shunted. All fire zones that
have alarmed will continue to show on all keypads
until a fire reset is performed, even if they have
physically restored. Fire zones may not be
bypassed using the BYPASS command.
address 10), force arming is possible when
the fire zone is violated (shorted).
ignored during the entry delay period. If it is violated
when the system is armed, it will activate a delay for
the programmed entry delay time. The keypad pre-
alert sounders will activate and the alarm system
may be disarmed during this delay period. If the
system is not disarmed during this delay period, this
zone will activate an alarm.
perimeter instant zone when the system is armed.
When the system is disarmed, any violation of this
zone will activate the keypad sounders which will
sound continuously until a disarm sequence is
entered. The alarm outputs for this zone will not
activate and there will be no report sent for this
zone when the system is disarmed. This zone will
report a trouble condition if programmed.