4/98
6<67(029(59,(:
The DS7060 Control/Communicator is a fully
integrated hard-wire security and residential fire alarm
system. It can support up to 6 input zones and 15
individual users. Up to 4 keypads may be used to
provide user interface with the system, as well as
programming access for the installer.
63(&,),&$7,216
 (QFORVXUH +RXVLQJ
The enclosure is manufactured from 22 Ga. (0.65
mm), cold-rolled steel, and measures 9.25" Wide, by
10.25" High, by 3" Deep (23.5 cm Wide, by 26 cm
High, by 7.6 cm Deep). The door has a knockout for a
standard DS lock (optional). The enclosure has a slot
in the back and also has an optional tamper switch
mounting bracket with a plunger switch.
 7HPSHUDWXUH
• Operating temp:
+32° to +120°F (0° to +49°C)
• Storage temp:
-20° to +150°F (-28° to +66°C)
 3RZHU
• Input Power: 16.5 VAC (U.S.) 16 VAC (Aust), 20
VA, 50 or 60 Hz
• Auxiliary Regulated Power:
• Auxiliary Power Voltage Range:
• Optional Standby battery (P334):
• Control Panel Current Draw:
• DS7443 Keypad Current Draw:
• DS7445 Keypad Current Draw: 75 mA, Standby
• DS7447 Keypad Current Draw:
• Fuse 1 and 2:
 2XWSXWV
• Programmable Output 1*: Solid state, switch to
ground (500 mA max.).
• Programmable Output 2*: Solid state, switch to
ground (500 mA max.).
• Programmable Output 3*: Form "C" relay contacts
available. Typical: Normally Open contacts that
switch to 12 V @ 800 mA.
* = Current draw should be subtracted from either
maximum auxiliary or maximum alarm current
draw.
Refer to Section 6.8 for detailed Output operation.
Page 2
12-12.5 VDC, 0.8 A
10 to 13.8 VDC
12 V, 7.0 AH
65 mA
45 mA, Standby
45 mA, Alarm
75 mA, Alarm
100 mA, Standby
100mA, Alarm
1 A, 250 V
Copyright © 1997-98 Detection Systems, Inc.
 =RQHV
• 6 zones (9 if Zone Doubling is used)
• Zone Response Time: All six zones can be
programmed to respond at either 300 ±100 ms or a
programmable time (common to all zones) that can
be configured to be between 10 ms and 2.5
seconds. Zones are ignored for 15 seconds after
power up, and for two seconds after a system reset.
Refer to Sections 6.2 - 6.7 for detailed zone operation.
 .H\SDGV
• Total number of keypads:
• Max. wire length total in system:
• Wire type:
NOTE: Keypads may be up to 1000 ft. (305 m) from
the panel when #22 (0.8 mm) wire is used
and only one keypad is connected to a
particular wire run.
 &RPPXQLFDWRU
Will report to two phone numbers with full single,
double, and backup reporting. Communicated in 3/1,
3/1E, 3/1 with Parity, 3/1E with Parity, 4/1, 4/2, High
Speed 4/9, Pager, Contact ID, and Personal Dialing
formats.
Refer to Sections 6.14 - 6.33 for communicator
operation.
The ringer equivalence is 0.1 B.
 8VHUV
The system allows up to 15 individual users. Each
user will have his own PIN number (the 4 digit code
entered at the keypads).
 /LJKWQLQJ 3URWHFWLRQ
MOVs and/or spark gaps provide protection from
lightning surges and static discharges.
 %XUJODU)LUH =RQH ,QSXWV
• Number of Circuits:
• End-of-Line Resistor:
NOTE: 4 wire type smoke detectors only.
 /LQH 6HL]XUH 1RWLFH
This control panel incorporates a line seizure feature
which will disable internal telephone lines when the
control panel is sending alarm or supervision reports
to the central station.
4 Keypads
1000 ft. (305 m)
22 AWG (0.8 mm)
6 Circuits on board
2.21k ohms
DS7060-AUS Reference Guide