I M P O R T A N T
When operating on Manchester networks, the dome can be programmed to respond to any of
the four available alarm inputs. However, the alarm input states cannot be transmitted to the
host controller. If transmitting the alarm input state to the host controller is required, the
alarm device must be wired directly to the host controller.
Setting Alarm Input States
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Set Alarm States.
3. Select the appropriate input line, and then change the setting.
Select Open if the alarm normal input state is open.
Select Closed if the alarm normal input state is closed.
The default setting is Open.
4. Repeat step 3 for each input requiring change. When finished, continue with step 5.
5. Select Exit to return to the Alarms/Areas/Home/Presets/PZ screen.
6. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit. The Dome
Configuration Menu appears. Continue with What To Do Next on page 4-20.
4-6
Note:
In most cases, the normal input state for a dome's input should match
the contact type of the connected switch.
SpeedDome Ultra VII Operator's Manual