Pacific energy The Esteem Installation And Operating Instructions Manual
Pacific energy The Esteem Installation And Operating Instructions Manual

Pacific energy The Esteem Installation And Operating Instructions Manual

Series c direct vent fireplace

Advertisement

IMPORTANT:
THESE INSTRUCTIONS ARE TO
REMAIN WITH THE
HOMEOWNER
FOR YOUR SAFETY
WARNING:
If the information in this
manual is not followed exactly, a fi re or
explosion may result causing property
damage, personal injury or loss of life.
-- Do not store or use gasoline or other
fl ammable vapors and liquids in the vicinity
of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
f i r e - p a r t s . c o m
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
• If you cannot reach your gas supplier,
call the fi re department.
-- Installation and service must be
performed by a qualifi ed installer, service
agency or the gas supplier.
This appliance may be installed in
an aftermarket permanently located,
manufactured (mobile) home, where not
prohibited by local codes.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certifi ed kit is used.
040706-44
Esteem
DIRECT VENT FIREPLACE
INSTALLATION
AND OPERATING
INSTRUCTIONS
ESTEEM_CM
The
SERIES C
ESMC.BODYAM
5056.411.C1

Advertisement

Table of Contents
loading

Summary of Contents for Pacific energy The Esteem

  • Page 1 IMPORTANT: THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER FOR YOUR SAFETY WARNING: If the information in this manual is not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life. -- Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
  • Page 2: Table Of Contents

    Contents CAUTION ..........................3 SAFETY ..........................3 MAINTENANCE ........................3 IMPORTANT NOTE FOR THE COMMONWEALTH OF MASSACHUSETTS: ....4 TOP STANDOFFS ......................6 INSTALLATION REQUIREMENTS ..................6 FRAMING ..........................6 FRAMING FOR SCREEN FRONT ..................7 PROPANE CONVERSION ....................8 TOP OR REAR VENT .......................
  • Page 3: Caution

    CAUTION MAINTENANCE FOR YOUR SAFETY - Do not install or operate your Pacifi c Energy Caution: Turn off gas and electrical power supply and allow ample fi replace without fi rst reading and understanding this manual. Any time for unit to cool before servicing appliance. It is recommended installation or operational deviation from the following instructions that this appliance and venting should be inspected at least once a voids the Pacifi c Energy Warranty and may prove hazardous.
  • Page 4: Important Note For The Commonwealth Of Massachusetts

    IMPORTANT NOTE FOR THE COMMONWEALTH OF MASSACHUSETTS: From Massachusetts Rules and Regulations 248 CMR 5.08: For all side wall horizontally vented gas fuelled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfi ed.
  • Page 5 Fig. # 2 Minimum Clearances to Combustibles: I L I Side standoffs ...... 0 in. (0 mm) Back standoffs ..... 0 in. (0 mm) Top standoffs ....... 0 in. (0 mm) Adjacent sidewall ....0 in. (0 mm) Ceiling to appliance ... 24 in. (610 mm) Mantel to appliance ..See Figure # 3 and 3a Maximum mantel extension ..
  • Page 6: Top Standoffs

    14 3/4" (375 mm) 15 1/2" (394 mm) FRAMING In planning the installation for the Esteem Fireplace, it is necessary Fig. # 3d Extended to determine where the unit is to be installed, location of vent system Top Standoffs and where gas supply piping may be plumbed. Various installations are possible, such as, into an existing wall, a corner, a built-in wall or a wall projection (see Fig.
  • Page 7: Framing For Screen Front

    If one is desired, the hearth extension may be up to 3/8 inch thick, if thicker, the fi replace In planning the installation for the Esteem Fireplace, it is necessary must be spaced up accordingly.
  • Page 8: Propane Conversion

    8" Concrete PROPANE CONVERSION Board Using the components shown in Fig. #7, the Esteem Direct Vent Fireplace can be converted to Propane Gas as follows: Burner Orifi ce Ensure the burner, pilot and gas supply are turned off and the appliance has cooled.
  • Page 9 8) Remove fi xed air shutter by removing screw. Reassemble with Fig. # 8 Grate Assembly adjustable air shutter only. (Fig. #11) Attachment Points Fig. # 11 Natural Gas Propane 5) Remove the two screws holding the burner bracket in place. (Fig. Remove This Non-Adjustable Shutter For LP Fig.
  • Page 10 4) Re-attach the burner tray to fi replace using the two wing nuts, and reconnect the gas supply. Fig. # 13 Hex Key Fig. # 15 Valve Conversion 1) Remove gas the supply line to the burner. f i r e - p a r t s . c o m 2) Remove the two wing nuts securing the burner tray to the fi replace and remove from the fi replace.
  • Page 11 9) Reassemble the valve cover and all other components. Note: Fig. # 17 Ensure that the pressure tapping screw is tight. LIGHT THE APPLIANCE AND THOROUGHLY LEAK-TEST ALL CONNECTIONS. VERIFY PROPER BURNER IGNITION AND OPERATION. Conversion Label In the white area on the conversion label, fi ll in the date and the name of the person who performed the conversion.
  • Page 12: Top Or Rear Vent

    Fig. # 21 Caution: The unused vent outlet must be blocked with the vent cover plate and gasket. Vent The Esteem is capable of top or rear vent applications. The fi replace Adapter is factory set for top vent application. Adapter...
  • Page 13 Fig. # 22 Vent system components approved for use with the Esteem Fireplace are shown in Appendix A. The Esteem Fireplace is also tested and certifi ed for use with SIMPSON DURA-VENT DIRECT VENT GS pipe Vent or SECURITY CHIMNEYS SECURE VENT system (see Optional Cover Plate Venting section).
  • Page 14 Fig. # 24 Fig. # 25 24" 45˚ Top View Top View Corner Vent HORIZONTAL RUN Fig. # 26 MAX. WALL f i r e - p a r t s . c o m TERMINATION VENTING CHART NOTE: The vent must not exceed a total length of 20 feet.
  • Page 15 Fig. # 27 ROOF TERMINATION MAX. VENTING CHART NOTE: The vent must not exceed a total length of 40 feet. Any com- bination of rise and run may be used but must be constrained to the boundaries of this chart. For each additional 90°...
  • Page 16: Vent System Restrictor Adjustment

    VENT SYSTEM RESTRICTOR ADJUSTMENT Fig. # 28c Located on the fi rebox rear wall are vent restrictors. The unit leaves the factory with the restrictors wide open as shown in Fig. #28b. These are built into the appliance for combustion air fl ow rate adjustment. WALL AND ROOF Adjustment of these restrictors ensures proper fl ame appearance for TERMINATION...
  • Page 17: Flex Vent Connection

    Fig. # 29 FLEX VENT CONNECTION It is best to locate the fi replace in position and attach the venting before doing any framing. The fl exible vent pipe may be stretched and/or cut to length as required. The 4 inch fl exible inner pipe must be centred inside the 8 inch pipe with pipe spacers provided.
  • Page 18: Vent Terminal Installation

    Fig. # 32 VENT TERMINAL WALL THIMBLE FRAME A 10 1/2" ROUND OR SQUARE HOLE f i r e - p a r t s . c o m * Minimum distance from the fi nished fl oor to the center of the opening varies with top or rear venting and vent system used.
  • Page 19: Roof Vent Terminal Installation

    VENT TERMINAL MINIMUM Fig. # 34 CLEARANCES INSIDE CORNER DETAIL FIXED CLOSED OPERABLE FIXED CLOSED OPERABLE AREA WHERE TERMINAL GAS METER VENT TERMINAL AIR SUPPLY INLET IS NOT PERMITTED Canadian Installations US Installations Canadian Installations US Installations A= Clearances above grade, 12 inches (30 cm) 12 inches (30 cm) I= Clearance to service regu-...
  • Page 20 Fig. # 36 SUPPORT SLEEVE 1/4" NUT AND WASHER 1/4" X 1" CARRIAGE BOLTS f i r e - p a r t s . c o m ROOF BRACKET Note: Adjustable for various roof pitches, from fl at roof to 12/12 pitch roof.
  • Page 21: Optional Venting

    12/12 pitch roof. OPTIONAL VENTING Wall Termination Venting The Esteem Fireplace is also tested and certifi ed for use with SIMPSON DURA-VENT DIRECT VENT GS pipe or SECURITY CHIMNEYS SECURE VENT system. Kits for venting either through the side wall The fi replace may be vented out the top or rear.
  • Page 22: Manufactured (Mobile) Home

    MANUFACTURED (MOBILE) HOME are maintained (see Fig. # 34). In some jurisdictions, the Esteem Fireplace may be installed in Where a vent pipe passes through a combustible wall, a wall thimble Manufactured Homes after the "fi rst sale". Consult local codes for must be used to hold insulation away and maintain a 1 inch clearance.
  • Page 23: Gas Supply

    SECURE VENT 36" - SV4STC36 14" - SV4STC36 PACIFIC ENERGY FLEX VENT f i r e - p a r t s . c o m * Minimum distance from the fi nished fl oor to the center of the opening varies with top or rear venting and vent system used.
  • Page 24: Optional Brick Panels Installation

    OPTIONAL BRICK PANELS INSTALLATION BURNER REMOVAL Decorative brick panels are to be installed after the burner is in place. Caution: Turn off gas and electrical power supply and allow ample (See Fig. #43) time for the unit to cool before proceeding. Unpack and inspect brick panels.
  • Page 25: Log Set Assembly

    LOG SET ASSEMBLY Step 1 Fig. # 45 Ember Floor PN# 5097.26105 Unpack and inspect log set. There should be a total of 7 logs, one ember bed and two base brick panels. Gas and vent connections should be completed before installing the log set. Position the logs, ember bed and base bricks as indicated by pictures below.
  • Page 26 Fig. # 46 Fig. # 47 Step 5 Step 7 Middle Front Log PN# 5097.23 Right Front Chunk PN# 5097.2614 Step 8 Left Front Chunk Step 6 PN# 5097.2613 Left Front Log PN# 5097.25 f i r e - p a r t s . c o m Fig.
  • Page 27: Optional Blower

    OPTIONAL BLOWER 115 VOLTS Fig. # 49 Electrical Supply: 60 Hz It is recommended that the fi replace electrical receptacle box be 0.5 AMPERES prewired during installation The optional blower (kit # ENCD.BLOW) ROCKER SNAP DISC is equipped with a three prong power cord and may be installed and SWITCH SWITCH plugged in at a later date.
  • Page 28 SCREEN DOOR INSTALLATION WARNING: Non-combustible facing material and extended top stand- Slide the spring nuts (supplied) over the slotted holes in the outer frame, offs must be used if the Optional Screen Door is to be installed. one in each corner. Do not install the Optional Screen Door onto an Esteem Fireplace Position the Screen Door in place and fasten to the outer frame with the that was framed in without the extended top standoffs and non-com-...
  • Page 29: Lighting Instructions

    LIGHTING INSTRUCTIONS f i r e - p a r t s . c o m 040706-44 ESTEEM_CM...
  • Page 30: Remote Operation

    REMOTE OPERATION 3) Timer setting The Broadway Direct Vent Insert comes equipped with a thermostatic remote control. The third option is to program the fi replace to operate at set times. It Once a pilot light has been established, and the gas control knob has two "on"...
  • Page 31: First Fire

    FIRST FIRE FLAME ADJUSTMENT When lit for the fi rst time, the appliance will emit a slight odour for The air shutter on the burner venturi tube controls the primary combustion a couple of hours. This is due to the curing of paints, sealants and air to the gas burner.
  • Page 32: Replacement Parts

    REPLACEMENT PARTS (WHEN ORDERING, INCLUDE PART NUMBER WITH DESCRIPTION) ITEM DESCRIPTION PART NO. ITEM DESCRIPTION PART NO. 1....REPLACEMENT GLASS ......GLAS.2075 11c ..FACING TRIM, RIGHT ......ENCD.27176 _ _ 2....WINDOW GASKET KIT ........2075.1 11d..BOTTOM TRIM BAR ......ENCD.27231 _ _ 3....WINDOW FRAME ........ENCD.2726 12....FRONT FRAME ...........ENCD.2714 4....FRONT TRIM, GOLD (2 pcs.
  • Page 33: Burner Replacement Parts

    BURNER REPLACEMENT PARTS (WHEN ORDERING, INCLUDE PART NUMBER WITH DESCRIPTION) ITEM DESCRIPTION PART NO. ITEM DESCRIPTION PART NO. 1....GRATE ASSEMBLY ........ESMC.2823 12....BURNER TRAY ASSEMBLY ...... ESMC.2810 2....BURNER DUAL FUEL .........5011.9 13....BURNER MOUNTING BRACKET ......2811.02 3....ORIFICE, #45, NG ..........5021.34 14....30” NG51 3F PILOT ASS’Y ......5009.156 4....MANIFOLD ASSEMBLY .......
  • Page 34: Appendix A

    APPENDIX A Louver Kit Installation Guide The ESTEEM METALLIC BLACK ENCD.LVMBK BRASS FINISH ENCD.LVBRA PORCELAIN BLACK ENCD.LVPBK Tools: PORCELAIN BLUE ENCD.LVPBE PORCELAIN GREEN ENCD.LVPGN (screwdrivers) PORCELAIN IVORY ENCD.LVPIY PORCELAIN RED ENCD.LVPRD #2 Robertson OR #2 Phillips PORCELAIN GRAPHITE ENCD.LVPGT This kit contains: 1..Top Louver...
  • Page 35: Optional Front Facing Trim

    Optional Front Facing Trim Installation Guide This kit contains: 1..Top Panel f i r e - p a r t s . c o m 1..Left Side Panel 1..Right Side Panel 6..#8 x 1/2" sheet metal screws (black in colour) 9..
  • Page 36 Installation Spring nut Fig. # 1 Unpack and inspect all parts. A fl athead or a #2 Rob- ertson screwdriver is required to install this kit. The facing trim kit must be installed before the top and bottom louvers. If the louvers are not installed, pro- ceed to step 3.
  • Page 37: Optional Remote Control Installation

    Optional Remote Control Installation Caution: DO NOT connect the batteries to the remote control receiver until the all of the wires are connected to the gas valve as a short circuit could result in damage to the electrical components of the remote control.
  • Page 38: Optional Blower Kit

    Optional Blower Kit ESTEEM ENCD.BLOW This kit contains: 1..Blower assembly 1 ..Speed Control box pre-wired with: -Power cord -Thermo-switch -Manual / Auto switch Blower Assem- f i r e - p a r t s . c o m Power Cord Speed Control 2..
  • Page 39: Wall Termination Kit

    Wall Termination Kit GASC.WALKIT This vent kit is for use with the ESTATE and the ESTEEM model fi replaces. Please refer to the Installation Instructions provided with the appliance for proper venting installation. This box contains: 1 ..Horizontal Vent Terminal 4 ..
  • Page 40: 5' Vent Pipe Kit

    5' Vent Pipe Kit ESTD.VP05 This vent kit is for use with the ESTATE and the ESTEEM model fi replaces only. Please refer to the Installation Instructions provided with the appliance for proper venting installation. This box contains: 5' ..4" Flex Vent 3 ..
  • Page 41: 10' Vent Pipe Kit

    10' Vent Pipe Kit ESTD.VP10 This vent kit is for use with the ESTATE and the ESTEEM model fi replaces only. Please refer to the Installation Instructions provided with the appliance for proper venting installation. This box contains: 10' .... 4" Flex Vent 1 ....
  • Page 42: Roof Termination Kit

    Roof Termination Kit ESTD.ROTKIT This vent kit is for use with the ESTATE and the ESTEEM model fi replaces. Please refer to the Installation Instructions provided with the appliance for proper venting installation. This box contains: 1 ..Roof Vent Terminal 3 ..
  • Page 43: Safety Label

    Canada and U.S.A. MADE IN CANADA FABRIQUE AU CANADA This Appliance is Equipped For Use With / MODEL/ SERIES/ Cet Appareil est Équipé Pour Utilise Avec : THE ESTEEM MODELE: SERIE: NATURAL GAS LP-GAS GAZ NATUREL LP GAZ FOR USE WITH/...
  • Page 44 f i r e - p a r t s . c o m Pacifi c Energy Fireplace Products Ltd. Phone: 1-877-715-2664 www.pacifi cenergy.net 2975 Allenby Rd., Duncan, B.C. V9L 6V8 Printed in Canada ESTEEM_CM 040706-44...

Table of Contents